Exergoeconomic analysis of carbon dioxide transcritical refrigeration machines

被引:117
作者
Fazelpour, Farivar [1 ]
Morosuk, Tatiana [2 ]
机构
[1] Islamic Azad Univ, Dept Energy Syst Engn, South Tehran Branch, Tehran, Iran
[2] Tech Univ Berlin, Inst Energy Engn, D-10587 Berlin, Germany
来源
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID | 2014年 / 38卷
关键词
Transcritical refrigeration machine; Carbon dioxide; Exergy analysis; Economic analysis; Energetic analysis; Exergoeconomic analysis; CO2; HEAT-PUMP; EXERGY ANALYSIS; SYSTEM; TEMPERATURE; PERFORMANCE; EQUATION;
D O I
10.1016/j.ijrefrig.2013.09.016
中图分类号
O414.1 [热力学];
学科分类号
摘要
In the last two decades many scientific papers and reports have been published in the field of the application of the carbon dioxide as a refrigerant for refrigeration (heat pump) systems. A simple transcritical CO2 refrigeration machine is evaluated from the perspectives of energetic, exergetic, economic and exergoeconomic analyses. Special attention has been paid to the transcritical cycle under hot climatic conditions. The main goal of this paper is to define the energy and cost efficient transcritical CO2 refrigeration machine, therefore the options for the structure and parametric improvements are discussed. Introducing the economizer as an auxiliary component for one-stage transcritical CO2 refrigeration machine helps us to decrease the total cost of the final product by approximately 14%. (C) 2013 Elsevier Ltd and IIR. All rights reserved.
引用
收藏
页码:128 / 139
页数:12
相关论文
共 35 条
  • [31] Definitions and nomenclature in exergy analysis and exergoeconomics
    Tsatsaronis, George
    [J]. ENERGY, 2007, 32 (04) : 249 - 253
  • [32] Recent developments in exergy analysis and exergoeconomics
    Tsatsaronis, George
    [J]. INTERNATIONAL JOURNAL OF EXERGY, 2008, 5 (5-6) : 489 - 499
  • [33] Modelling the performance of a transcritical CO2 heat pump for high temperature heating (Reprinted)
    White, SD
    Yarrall, MG
    Cleland, DJ
    Hedley, RA
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2002, 25 (04): : 479 - 486
  • [34] Influence of ambient temperatures on performance of a CO2 heat pump water heating system
    Yokoyama, Ryohei
    Shimizu, Takeshi
    Ito, Koichi
    Takemura, Kazuhisa
    [J]. ENERGY, 2007, 32 (04) : 388 - 398
  • [35] Theoretical and experimental studies on optimum heat rejection pressure for a CO2 heat pump system
    Zhang, X. P.
    Fan, X. W.
    Wang, F. K.
    Shen, H. G.
    [J]. APPLIED THERMAL ENGINEERING, 2010, 30 (16) : 2537 - 2544