Loss of excitation of synchronous generator

被引:8
作者
Kristof, Vladimir [1 ]
Mester, Marian [2 ]
机构
[1] Power Syst Management Sro, Ondavska 5, Kosice 04001, Slovakia
[2] Vchodoslovenska Distribucna As, Distribut Co, Distribut Syst Operat Sect, Mlynska 31, Kosice 04001, Slovakia
来源
JOURNAL OF ELECTRICAL ENGINEERING-ELEKTROTECHNICKY CASOPIS | 2017年 / 68卷 / 01期
关键词
loss of excitation; excitation system; synchronous generator; stability;
D O I
10.1515/jee-2017-0007
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents results of study of loss-of-excitation phenomena simulations. Loss of excitation is a very common fault in synchronous machine operating and can be caused by short circuit of the field winding, unexpected field breaker open or loss-of-excitation relay mal-operation. According to the statistic [1], the generator failure due to loss-of-excitation accounts for 69% of all generator failures. There has been concern over possible incorrect operation of the relay when operating the generator in the under-excited region, during stable transient swings and during major system disturbances. This article can serve as inputs for system operators in preparation of operation area or protection relaying area.
引用
收藏
页码:54 / 60
页数:7
相关论文
共 12 条
[1]  
Anderson PM, 1977, Power system control and stabilityJ
[2]  
[Anonymous], 2006, C371022006 IEEE
[3]   LOSS OF EXCITATION PROTECTION FOR MODERN SYNCHRONOUS GENERATORS [J].
BERDY, J .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1975, 94 (05) :1457-1463
[4]   INFLUENCE OF GENERATOR LOSS OF EXCITATION ON BULK POWER-SYSTEM RELIABILITY [J].
DARRON, HG ;
KOEPFINGER, JL ;
MATHER, JR ;
RUSCHE, PA .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1975, 94 (05) :1473-1483
[5]  
Dohnalek P., 1991, OCHRANY PRO PRUMYSL
[6]  
Hora O., 1985, REGULACNI BUDICI SYS
[7]  
JANICEK F, 2004, DIGITALNE OCHRANY EL
[8]  
Maslo K., 1997, P 4 INT WORKSH EL PO
[9]  
Maslo K., 2002, 5 MEZ K CP HS 2002 Z
[10]  
Shi Z, 2010, INVESTIGATION GENERA