Annual operating energy savings of liquid desiccant and evaporative-cooling-assisted 100% outdoor air system

被引:61
作者
Kim, Min-Hwi [1 ]
Park, Joon-Young [1 ]
Sung, Min-Ki [3 ]
Choi, An-Seop [2 ]
Jeong, Jae-Weon [1 ]
机构
[1] Hanyang Univ, Div Architectural Engn, Seoul 133791, South Korea
[2] Sejong Univ, Dept Architectural Engn, Seoul 143747, South Korea
[3] Sejong Univ, Dept Architectural Engn, Seoul 143791, South Korea
基金
新加坡国家研究基金会;
关键词
Evaporative cooling; Liquid desiccant; 100% outdoor air system; Water-side free cooling; Solar thermal system; VENTILATION PRECONDITIONING SYSTEM; MASS-TRANSFER; PACKED-COLUMN; DEHUMIDIFICATION; PERFORMANCE; HEAT; DEHUMIDIFIER/REGENERATOR;
D O I
10.1016/j.enbuild.2014.03.006
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The purpose of this research is to investigate the annual operating energy performance of a desiccant and evaporative-cooling-assisted 100% outdoor air system. The seasonal mode of operation of the proposed system is also suggested and used for estimating the energy saving potentials. The TRNSYS 16 program integrated with a commercial equation solver is used for the energy simulation of the proposed system, and then two existing air handling alternatives: a conventional variable air volume (VAV) system and an existing evaporative-cooling-assisted system are compared with the proposed system. The proposed system shows operating energy savings of 82% over the conventional VAV system during the summer, and 54% and 37% in the winter and the intermediate season operations, respectively. Ultimately, the proposed system provides 68% annual operating energy saving over the conventional VAV system, and 23% savings compared to the established evaporative-cooling-assisted system. It is also found that the extreme energy benefit can be obtained by enhancing the evaporative cooling effects using the liquid desiccant (LD) unit. The operating energy saving of the LD unit can be achieved by applying the water-side free cooling and the solar thermal system. (C) 2014 Elsevier B.V. All rights reserved.
引用
收藏
页码:538 / 550
页数:13
相关论文
共 32 条
[1]   Performance of a solar liquid desiccant air conditioner - An experimental and theoretical approach [J].
Alizadeh, Shahab .
SOLAR ENERGY, 2008, 82 (06) :563-572
[2]  
[Anonymous], 1998, NRELTP55024688
[3]  
[Anonymous], 2009, ASHRAE Handbook|Fundamentals
[4]   An analytical solution for air dehumidification by liquid desiccant in a packed column [J].
Babakhani, Davoud ;
Soleymani, Meysam .
INTERNATIONAL COMMUNICATIONS IN HEAT AND MASS TRANSFER, 2009, 36 (09) :969-977
[5]   Analytical solution of adiabatic heat and mass transfer process in packed-type liquid desiccant equipment and its application [J].
Chen, X. Y. ;
Li, Z. ;
Jiang, Y. ;
Qu, K. Y. .
SOLAR ENERGY, 2006, 80 (11) :1509-1516
[6]   Vapor pressures of the aqueous desiccants [J].
Chung, TW ;
Luo, CM .
JOURNAL OF CHEMICAL AND ENGINEERING DATA, 1999, 44 (05) :1024-1027
[7]   Comparison between random and structured packings for dehumidification of air by lithium chloride solutions in a packed column and their heat and mass transfer correlations [J].
Chung, TW ;
Ghosh, TK ;
Hines, AL .
INDUSTRIAL & ENGINEERING CHEMISTRY RESEARCH, 1996, 35 (01) :192-198
[8]   PREDICTIONS OF MOISTURE REMOVAL EFFICIENCIES FOR PACKED-BED DEHUMIDIFICATION SYSTEMS [J].
CHUNG, TW .
GAS SEPARATION & PURIFICATION, 1994, 8 (04) :265-268
[9]   Study of an aqueous lithium chloride desiccant system: Air dehumidification and desiccant regeneration [J].
Fumo, N ;
Goswami, DY .
SOLAR ENERGY, 2002, 72 (04) :351-361
[10]   Experimental investigation of a liquid desiccant system for solar cooling and dehumidification [J].
Gommed, K. ;
Grossman, G. .
SOLAR ENERGY, 2007, 81 (01) :131-138