Effect of load type on standalone micro grid fault performance

被引:14
作者
Kamel, Rashad M. [1 ,2 ]
Nagasaka, Ken [3 ]
机构
[1] Kuwait Univ, Dept Elect Engn, Coll Engn & Petr, Safat 13060, Kuwait
[2] Assiut Univ, Dept Elect Engn, Fac Engn, Assiut, Egypt
[3] Tokyo Univ Agr & Technol, Environm Energy Engn, Koganei, Tokyo, Japan
关键词
Stand alone MG; MG fault performance; Dynamic loads; Static loads; Protective device ratings and settings; MANAGEMENT; STABILITY; SYSTEMS; MODELS; RIDE;
D O I
10.1016/j.apenergy.2015.09.044
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This paper studies the influence of the load type on the fault performance of the standalone Micro Grid (MG). Different load types (static and dynamic) are considered to show their effects on the standalone MG fault behavior. Specifically, the effects of constant power static loads, constant impedance static loads, and constant current static loads are analyzed. Also, effects of dynamic (rotating) loads are highlighted. Results show, that the rotating loads have dominant effects on the fault performance of the MG during the standalone (islanded) mode. Furthermore, rotating loads cause fault currents and touch voltages three times the values associated with the static loads. Consequently, the employed protective devices with the rotating loads MG must be rated three times larger than the employed protective devices with the static loads MG. Also, the time settings of the MG protection devices are highly influenced with the load type. For static load MG, it is equal to 250% of the rotating loads MG protection devices time settings. The three types of static load show different impacts on islanded MG fault performance. Constant power static load has the highest effect compared to the other two static load types (namely, constant impedance and constant current static loads). The results obtained in this study provide a guide for the MG protection designers and planners to consider the effects of load type on the MG protection devices rating and setting. (C) 2015 Elsevier Ltd. All rights reserved.
引用
收藏
页码:532 / 540
页数:9
相关论文
共 32 条
  • [1] Abdel-Salam Mazen, 2013, P INTELEC R C HAMB B, P458
  • [2] Al-Nasseri H., 2006, 2006 IEEE Power Engineering Society General Meeting, P7
  • [3] [Anonymous], 1992, 12089 EPRI
  • [4] [Anonymous], THESIS
  • [5] [Anonymous], 2006, 50003024 CONS EL REL
  • [6] [Anonymous], 2009, IEEE INT C POW SYST
  • [7] A novel off-grid hybrid power system comprised of solar photovoltaic, wind, and hydro energy sources
    Bhandari, Binayak
    Lee, Kyung-Tae
    Lee, Caroline Sunyong
    Song, Chul-Ki
    Maskey, Ramesh K.
    Ahn, Sung-Hoon
    [J]. APPLIED ENERGY, 2014, 133 : 236 - 242
  • [8] Short-circuit calculations in networks with distributed generation
    Boutsika, Thekla N.
    Papathanassiou, Stavros A.
    [J]. ELECTRIC POWER SYSTEMS RESEARCH, 2008, 78 (07) : 1181 - 1191
  • [9] Economic analysis and optimal energy management models for microgrid systems: A case study in Taiwan
    Chen, Yen-Haw
    Lu, Su-Ying
    Chang, Yung-Ruei
    Lee, Ta-Tung
    Hu, Ming-Che
    [J]. APPLIED ENERGY, 2013, 103 : 145 - 154
  • [10] LOAD REPRESENTATION IN POWER SYSTEM STABILITY STUDIES
    CONCORDIA, C
    IHARA, S