Study on longitudinal temperature distribution of fire-induced ceiling flow in tunnels with different sectional coefficients

被引:83
作者
Liu, Fang [1 ,3 ,4 ]
Yu, Long Xing [1 ,2 ]
Weng, Miao Cheng [1 ,3 ,4 ]
Lu, Xin Ling [1 ]
机构
[1] Chongqing Univ, Fac Urban Construct & Environm Engn, Chongqing 400045, Peoples R China
[2] Ghent Univ UGent, Dept Flow Heat & Combust Mech, Sint Pietersnieuwstr 41, B-9000 Ghent, Belgium
[3] Minist Educ, Key Lab Three Gorges Reservoir Reg Ecoenvironm, Chongqing 400045, Peoples R China
[4] Natl Ctr Int Res Low Carbon & Green Bldg, Chongqing 400045, Peoples R China
关键词
Tunnel fire; Smoke temperature; CFD simulation; Small-scale model experiment; SMOKE TEMPERATURE; VENTILATION SYSTEMS; MOVEMENT; VELOCITY; GASES; TESTS; MODEL;
D O I
10.1016/j.tust.2016.01.031
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
This paper proposes two prediction models for the maximum smoke temperature rise and the temperature distribution in tunnel fires, in which sectional coefficient zeta was introduced to describe geometrical characteristic of the tunnel section. At first, the theoretical analysis was conducted. The dimensionless maximum smoke temperature rise was deduced by applying the dimensional analysis method while the smoke temperature exponential decay law was proposed based on the one-dimensional theory. Then, CFD simulations were conducted in nine tunnels with different cross sectional shapes by Fire Dynamics Simulator, version 5.5. With the 'numerical experiments', two prediction models for the maximum smoke temperature and the smoke temperature distribution were obtained. Meanwhile, complementary experiments were conducted in a 1/10 scale tunnel in order to provide a verification. The experiment results show a good agreement with the numerical simulations. Moreover, the proposed prediction models were compared with the prediction models proposed by Kurioka model and Li model. (C) 2016 Elsevier Ltd. All rights reserved.
引用
收藏
页码:49 / 60
页数:12
相关论文
共 26 条
[11]   Model scale railcar fire tests [J].
Ingason, Haukur .
FIRE SAFETY JOURNAL, 2007, 42 (04) :271-282
[12]   Model scale tunnel fire tests with longitudinal ventilation [J].
Ingason, Haukur ;
Li, Ying Zhen .
FIRE SAFETY JOURNAL, 2010, 45 (6-8) :371-384
[13]   Simple model for control of fire gases in a ventilated tunnel [J].
Kunsch, JP .
FIRE SAFETY JOURNAL, 2002, 37 (01) :67-81
[14]  
Kunsch JP, 1999, ATMOS ENVIRON, V33, P13
[15]   Fire properties in near field of square fire source with longitudinal ventilation in tunnels [J].
Kurioka, H ;
Oka, Y ;
Satoh, H ;
Sugawa, O .
FIRE SAFETY JOURNAL, 2003, 38 (04) :319-340
[16]   A numerical study on smoke movement in longitudinal ventilation tunnel fires for different aspect ratio [J].
Lee, SR ;
Ryou, HS .
BUILDING AND ENVIRONMENT, 2006, 41 (06) :719-725
[17]  
Li L., 2012, J FIRE SCI
[18]   Fire-induced flow temperature along tunnels with longitudinal ventilation [J].
Li, Liming ;
Li, Sen ;
Wang, Xuegui ;
Zhang, Heping .
TUNNELLING AND UNDERGROUND SPACE TECHNOLOGY, 2012, 32 :44-51
[19]   The maximum temperature of buoyancy-driven smoke flow beneath the ceiling in tunnel fires [J].
Li, Ying Zhen ;
Lei, Bo ;
Ingason, Haukur .
FIRE SAFETY JOURNAL, 2011, 46 (04) :204-210
[20]  
McGrattan K., 2008, NIST SPECIAL PUBLICA, V1019, P27