Rapid identification of multiple constantly-released contaminant sources in indoor environments with unknown release time

被引:34
作者
Cai, Hao [1 ]
Li, Xianting [2 ]
Chen, Zhilong [1 ]
Wang, Mingyang [1 ]
机构
[1] PLA Univ Sci & Technol, State Key Lab Explos & Impact & Disaster Prevent, Nanjing 210007, Jiangsu, Peoples R China
[2] Tsinghua Univ, Sch Architecture, Dept Bldg Sci, Beijing 100084, Peoples R China
基金
中国国家自然科学基金; 美国国家科学基金会;
关键词
Source identification; Contaminant source; Indoor environment; Computational fluid dynamics; Sensor; Air distribution; SOURCE LOCATION; TRACKING; HISTORY; CFD; SYSTEMS;
D O I
10.1016/j.buildenv.2014.06.006
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The sudden release of airborne hazardous contaminants in an indoor environment can potentially lead to severe disasters, such as the spread of toxic gases, fire, and explosion. To prevent and mitigate these disasters it is critical to rapidly and accurately identify the characteristics of the contaminant sources. Although remarkable achievements have been made in identifying a single indoor contaminant source in recent years, the issues related to multiple contaminant sources are still challenging. This study presents a method for identifying the exact locations, emission rates, and release time of multiple indoor contaminant sources simultaneously released at constant rates, by considering sensor thresholds and measurement errors. The method uses a two-stage procedure for rapid source identification. Before the release of contaminants, only a limited number of time-consuming computational fluid dynamics (CFD) simulations need to be conducted. After the release of contaminants, the method can be executed in real-time. Through case studies in a three-dimensional office the method was numerically demonstrated and validated, and the results show that the method is effective and feasible. The effects of sensor threshold, measurement error and total sampling time on the source identification performance were analysed, and the limitations and applicability of the method were also discussed. (C) 2014 Elsevier Ltd. All rights reserved.
引用
收藏
页码:7 / 19
页数:13
相关论文
共 51 条
[1]  
Alifanov O.M., 1994, Inverse Heat Transfer Problems
[2]   Utilizing state estimation to determine the source location for a contaminant [J].
Annunzio, Andrew J. ;
Young, George S. ;
Haupt, Sue Ellen .
ATMOSPHERIC ENVIRONMENT, 2012, 46 :580-589
[3]   State of the art report on mathematical methods for groundwater pollution source identification [J].
Atmadja, J ;
Bagtzoglou, AC .
ENVIRONMENTAL FORENSICS, 2001, 2 (03) :205-214
[4]   Multizone airflow Modeling in buildings: History and theory [J].
Axley, James .
HVAC&R RESEARCH, 2007, 13 (06) :907-928
[5]   Identification of Pollution Sources in Urban Areas Using Reverse Simulation with Reversed Time Marching Method [J].
Bady, Mahmoud ;
Kato, Shinsuke ;
Huang, Hong .
JOURNAL OF ASIAN ARCHITECTURE AND BUILDING ENGINEERING, 2009, 8 (01) :275-282
[6]   Contaminant source identification within a building: Toward design of immune buildings [J].
Bastani, Arash ;
Haghighat, Fariborz ;
Kozinski, Janusz A. .
BUILDING AND ENVIRONMENT, 2012, 51 :320-329
[7]   Fast Identification of Multiple Indoor Constant Contaminant Sources by Ideal Sensors: A Theoretical Model and Numerical Validation [J].
Cai, Hao ;
Li, Xianting ;
Chen, Zhilong ;
Kong, Lingjuan .
INDOOR AND BUILT ENVIRONMENT, 2013, 22 (06) :897-909
[8]  
Cai H, 2012, INT J VENT, V11, P155
[9]   Rapid identification of single constant contaminant source by considering characteristics of real sensors [J].
Cai Hao ;
Li Xian-ting ;
Kong Ling-juan ;
Ma Xiao-jun ;
Shao Xiao-liang .
JOURNAL OF CENTRAL SOUTH UNIVERSITY, 2012, 19 (03) :593-599
[10]   Decision analysis of emergency ventilation and evacuation strategies against suddenly released contaminant indoors by considering the uncertainty of source locations [J].
Cai, Hao ;
Long, Weiding ;
Li, Xianting ;
Kong, Lingjuan ;
Xiong, Shuang .
JOURNAL OF HAZARDOUS MATERIALS, 2010, 178 (1-3) :101-114