Voltage Stability and Transient Symmetrical Fault Current Control of Voltage-Controlled MMCs

被引:12
作者
Li, Yingbiao [1 ]
Guo, Jianbo [1 ]
Wu, Heng [2 ]
Wang, Xiongfei [2 ]
Zhao, Bing [1 ]
Wang, Shanshan [1 ]
Wu, Guanglu [1 ]
机构
[1] China Elect Power Res Inst, Beijing 100192, Peoples R China
[2] Aalborg Univ, Dept Energy Technol, DK-9220 Aalborg, Denmark
关键词
Voltage control; Regulators; Fault currents; Feedforward systems; Power system stability; Wind farms; Transient analysis; Modular Multilevel Converter (MMC); voltage control; controller design; fault current; HVDC; DESIGN; CONVERTERS;
D O I
10.1109/TPWRD.2020.2970247
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents a design-oriented analysis on the voltage stability and the transient fault current limitation of voltage-controlled modular multilevel converter (MMC) with L-filters. First, a dual-loop voltage control based on the L-filter plant is systematically designed, where the upper limits of controller parameters to ensure the small-signal stability are identified. Then, considering the transient current limitation during faults, the lower boundaries of inner current controller parameters are derived. Within the region of allowed controller parameters, the optimization is further made to minimize the closed-loop output impedance of MMC, which enhances the output voltage stiffness against the load current disturbance. Lastly, time-domain simulations corroborate the theoretical analysis.
引用
收藏
页码:2506 / 2516
页数:11
相关论文
共 31 条
[1]   Step-by-Step Controller Design for LCL-Type Grid-Connected Inverter with Capacitor-Current-Feedback Active-Damping [J].
Bao, Chenlei ;
Ruan, Xinbo ;
Wang, Xuehua ;
Li, Weiwei ;
Pan, Donghua ;
Weng, Kailei .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2014, 29 (03) :1239-1253
[2]   Fault Ride-Through Capability Enhancement Strategy for VSC-HVDC Systems Supplying for Passive Industrial Installations [J].
Bian, Zhipeng ;
Xu, Zheng .
IEEE TRANSACTIONS ON POWER DELIVERY, 2016, 31 (04) :1673-1682
[3]  
[卜广全 Bu Guangquan], 2017, [中国电机工程学报, Proceedings of the Chinese Society of Electrical Engineering], V37, P6303
[4]   Negative Sequence Current Control in Wind Power Plants With VSC-HVDC Connection [J].
Chaudhary, Sanjay K. ;
Teodorescu, Remus ;
Rodriguez, Pedro ;
Kjaer, Philip Carne ;
Gole, Ani M. .
IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, 2012, 3 (03) :535-544
[5]  
[管敏渊 Guan Minyuan], 2013, [电工技术学报, Transactions of China Electrotechnical Society], V28, P255
[6]   Fault characteristics and protection adaptability analysis in VSC-HVDC-connected offshore wind farm integration system [J].
Jia, Ke ;
Chen, Rui ;
Xuan, Zhenwen ;
Yang, Zhe ;
Fang, Yu ;
Bi, Tianshu .
IET RENEWABLE POWER GENERATION, 2018, 12 (13) :1547-1554
[7]   Enhanced AC voltage and frequency control of offshore MMC station for wind farm connection [J].
Jing, Yiran ;
Li, Rui ;
Xu, Lie ;
Wang, Yi .
IET RENEWABLE POWER GENERATION, 2018, 12 (15) :1771-1777
[8]   Offshore Wind Farm Modeling Accuracy and Efficiency in MMC-Based Multiterminal HVDC Connection [J].
Karaagac, U. ;
Mahseredjian, J. ;
Cai, L. ;
Saad, H. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2017, 32 (02) :617-627
[9]   Impedance Analysis of Modular Multi-Level Converters Connected to Weak AC Grids [J].
Khazaei, Javad ;
Beza, Mebtu ;
Bongiorno, Massimo .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2018, 33 (04) :4015-4025
[10]   Operation and Control Methods of Modular Multilevel Converters in Unbalanced AC Grids: A Review [J].
Li, Jinke ;
Konstantinou, Georgios ;
Wickramasinghe, Harith R. ;
Pou, Josep .
IEEE JOURNAL OF EMERGING AND SELECTED TOPICS IN POWER ELECTRONICS, 2019, 7 (02) :1258-1271