A Comparison of AC and HVDC Options for the Connection of Offshore Wind Generation in Great Britain

被引:72
作者
Elliott, Douglas [1 ]
Bell, Keith R. W. [2 ]
Finney, Stephen J. [2 ]
Adapa, Ram [3 ]
Brozio, Cornel [4 ]
Yu, James [4 ]
Hussain, Khadim [5 ]
机构
[1] Siemens Wind Power, Glasgow G2 8LR, Lanark, Scotland
[2] Univ Strathclyde, Glasgow G1 1XW, Lanark, Scotland
[3] EPRI, Palo Alto, CA 94304 USA
[4] Scottish Power Energy Networks, Glasgow G72 0HT, Lanark, Scotland
[5] Natl Grid Elect Transmiss, Warwick CV34 6DA, England
关键词
Cables; HVDC; power system economics; power system stability; reactive power; voltage control; wind energy; SYSTEM;
D O I
10.1109/TPWRD.2015.2453233
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents a comparison of two forms of cable connection of a distant offshore wind farm to a transmission system: AC and HVDC. The requirements of relevant industry standards in Great Britain (GB) that drive a connection design and, hence, its costs are highlighted along with an analysis of the ways in which AC cable connections might be made to comply while facilitating the export of active power. Dynamic studies investigating responses to grid-side short-circuit faults show that, in the particular scenarios studied, an AC connection of a wind farm in place of a large synchronous generator is marginally detrimental while an HVDC connection is beneficial. A comparison of costs shows that the crossover distance at which HVDC is cheaper than AC for wind farms of different sizes occurs at longer distances than have hitherto commonly been assumed, and AC connections benefit from reactive compensation not only at the point of common coupling and wind farm end, but also at the connection midpoint.
引用
收藏
页码:798 / 809
页数:12
相关论文
共 36 条
[31]   Economic comparison of VSC HVDC and HVAC as transmission system for a 300 MW offshore wind farm [J].
Van Eeckhout, B. ;
Van Hertem, D. ;
Reza, M. ;
Srivastava, K. ;
Belmans, R. .
EUROPEAN TRANSACTIONS ON ELECTRICAL POWER, 2010, 20 (05) :661-671
[32]  
Van Eeckhout B., 2008, The economic value of VSC HVDC compared to HVAC for offshore wind farms
[33]  
Wiechowski W, 2008, IEEE POW ENER SOC GE, P574
[34]  
Windatlas, 2013, EUR WIND RES OP SEA
[35]  
Zhang C., 2013, DEEP WAT OFFSH WIND
[36]  
2005, STUDY DEV OFFSHORE G