An analytical solution for air dehumidification by liquid desiccant in a packed column

被引:51
作者
Babakhani, Davoud [1 ]
Soleymani, Meysam [2 ]
机构
[1] Univ Isfahan, Fac Engn, Dept Chem Engn, Esfahan 8174673441, Iran
[2] Isfahan Univ Technol, Dept Chem Engn, Esfahan 8415683111, Iran
关键词
Dehumidifier; Liquid desiccant; Analytical solution; Packed column; MASS-TRANSFER PROCESSES; HEAT; PERFORMANCE; SYSTEM; MODEL;
D O I
10.1016/j.icheatmasstransfer.2009.06.002
中图分类号
O414.1 [热力学];
学科分类号
摘要
This paper presents a new analytical solution of heat and mass transfer processes in a packed bed liquid desiccant dehumidifier based on the equilibrium humidity on the interface is assumed to be constant. In order to maintain the partial pressure difference on the interface, a high liquid desiccant flow rate is often applied in the practical absorber. Therefore, for a narrow range of operating conditions for practical dehumidification process, we can assume that the equilibrium humidity ratio on the interface is constant. The assumption of constant humidity ratio is applied in this paper for derivation of the analytical solution. The model and the analytical solution predictions were compared against a reliable set of experimental data available in the literature, with very good agreement. According to the Lewis definition in this present study, the Lewis number obtains 0.9. The effects of variables such as air and liquid desiccant flow rate, air temperature and humidity, desiccant temperature and concentration have been investigated on the condensation rate. The results present that design variables such as desiccant concentration, desiccant temperature, air flow rate, and air humidity ratio have the greatest impact on the performance of the dehumidifier. The liquid flow rate and the a it temperature have not a significant effect. Furthermore, the effects of air and liquid desiccant flow rate have been reported on the humidity effectiveness of the column. (C) 2009 Elsevier Ltd. All rights reserved.
引用
收藏
页码:969 / 977
页数:9
相关论文
共 21 条
[1]   Effect of structured packing density on performance of air dehumidifier [J].
Abdul-Wahab, SA ;
Abu-Arabi, MK ;
Zurigat, YH .
ENERGY CONVERSION AND MANAGEMENT, 2004, 45 (15-16) :2539-2552
[2]   The effect of absorber packing height on the performance of a hybrid liquid desiccant system [J].
Ani, FN ;
Badawi, EM ;
Kannan, KS .
RENEWABLE ENERGY, 2005, 30 (15) :2247-2256
[3]   Analytical solution of adiabatic heat and mass transfer process in packed-type liquid desiccant equipment and its application [J].
Chen, X. Y. ;
Li, Z. ;
Jiang, Y. ;
Qu, K. Y. .
SOLAR ENERGY, 2006, 80 (11) :1509-1516
[4]  
Chung TW, 2000, SEPAR SCI TECHNOL, V35, P1502
[5]   Comparison between random and structured packings for dehumidification of air by lithium chloride solutions in a packed column and their heat and mass transfer correlations [J].
Chung, TW ;
Ghosh, TK ;
Hines, AL .
INDUSTRIAL & ENGINEERING CHEMISTRY RESEARCH, 1996, 35 (01) :192-198
[6]   PREDICTIONS OF MOISTURE REMOVAL EFFICIENCIES FOR PACKED-BED DEHUMIDIFICATION SYSTEMS [J].
CHUNG, TW .
GAS SEPARATION & PURIFICATION, 1994, 8 (04) :265-268
[7]   Dehumidification of air by chemical liquid desiccant in a packed column and its heat and mass transfer effectiveness [J].
Elsarrag, E .
HVAC&R RESEARCH, 2006, 12 (01) :3-16
[8]   Study of an aqueous lithium chloride desiccant system: Air dehumidification and desiccant regeneration [J].
Fumo, N ;
Goswami, DY .
SOLAR ENERGY, 2002, 72 (04) :351-361
[9]   A simplified model for air dehumidification with liquid desiccant [J].
Gandhidasan, P .
SOLAR ENERGY, 2004, 76 (04) :409-416
[10]   Performance analysis of liquid desiccant dehumidification systems [J].
Jain, Sanjeev ;
Bansal, P. K. .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2007, 30 (05) :861-872