Two-phase flow patterns, heat transfer and pressure drop characteristics of R600a during flow boiling inside a horizontal tube

被引:63
作者
Yang, Zhiqiang [1 ,2 ]
Gong, Maoqiong [1 ]
Chen, Gaofei [1 ]
Zou, Xin [1 ]
Shen, Jun [1 ]
机构
[1] Chinese Acad Sci, Tech Inst Phys & Chem, Key Lab Cryogen, Beijing 100190, Peoples R China
[2] Univ Chinese Acad Sci, Beijing 100049, Peoples R China
基金
中国国家自然科学基金;
关键词
R600a; Flow pattern; Flow boiling; Heat transfer; Pressure drop; New correlation; GENERAL CORRELATION; PREDICTIVE METHODS; VERTICAL TUBE; SMOOTH TUBES; AIR-WATER; PART I; REFRIGERANT; MIXTURES; CONDENSATION; HYDROCARBON;
D O I
10.1016/j.applthermaleng.2017.03.124
中图分类号
O414.1 [热力学];
学科分类号
摘要
A detailed experimental study was carried out to investigate the flow boiling heat transfer and pressure drop characteristics of R600a in a smooth horizontal tube with an inner diameter of 6 mm. The experiments were performed at conditions covering saturation pressures from 0.215 to 0.415 MPa, mass fluxes from 67 to 194 kg m(-2) s(-1) and heat fluxes from 10.6 to 75.0 kW m(-2). Based on an high speed camera, four main flow regimes can be observed: plug flow, stratified-wavy flow, slug flow and annular flow. Intermittent to annular flow transition was detected and plotted on flow pattern maps. Comparisons with available transition lines in the literature have been made. Furthermore, the influences of saturation pressure, mass flux and heat flux on heat transfer coefficient were analyzed. The experimental data was compared with the calculated data of seven well-known correlations. The results indicated that, the correlation of Liu and Winterton showed the best agreement with a mean absolute relative deviation of 11.5%. For two-phase frictional pressure drop, mass flux had obviously positive effect on frictional pressure drop, while negative effect was found for saturation pressure. Eight correlations were evaluated and the correlation of Mililler-Steinhagen and Heck gave the best fit to the experimental data with a mean absolute relative deviation of 32.9%. A new correlation of pressure drop which accounted for the influence of surface tension and gravitational force was developed on the basis of Milller-Steinhagen and Heck correlation and its mean absolute relative deviation was about 16.6% for the experimental data. (C) 2017 Elsevier Ltd. All rights reserved.
引用
收藏
页码:654 / 671
页数:18
相关论文
共 66 条
[1]  
Ahamed J.U., 2010, ENG E TRANSACTION, V5, P11
[2]   Experimental investigation of flow boiling heat transfer of R-600a/oil/CuO in a plain horizontal tube [J].
Akhavan-Behabadi, M. A. ;
Nasr, M. ;
Baqeri, S. .
EXPERIMENTAL THERMAL AND FLUID SCIENCE, 2014, 58 :105-111
[3]  
Anwar Z., 2013, EXP THERM FLUID SCI, V53, P1230
[4]  
BARBIERI P., 2008, P 5 EUR THERM SCI C
[5]   A composite heat transfer correlation for saturated flow boiling in small channels [J].
Bertsch, Stefan S. ;
Groll, Eckhard A. ;
Garimella, Suresh V. .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2009, 52 (7-8) :2110-2118
[6]   Two-phase pressure drop of air-water and R-410A in small horizontal tubes [J].
Chen, IY ;
Yang, KS ;
Chang, YJ ;
Wang, CC .
INTERNATIONAL JOURNAL OF MULTIPHASE FLOW, 2001, 27 (07) :1293-1299
[7]   CORRELATION FOR BOILING HEAT TRANSFER TO SATURATED FLUIDS IN CONVECTIVE FLOW [J].
CHEN, JC .
INDUSTRIAL & ENGINEERING CHEMISTRY PROCESS DESIGN AND DEVELOPMENT, 1966, 5 (03) :322-&
[9]   PRESSURE-GRADIENTS DUE TO FRICTION DURING FLOW OF EVAPORATING 2-PHASE MIXTURES IN SMOOTH TUBES AND CHANNELS [J].
CHISHOLM, D .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 1973, 16 (02) :347-358
[10]  
Collier JG., 1994, CONVECTIVE BOILING C