Investigation of a cascaded CO2 refrigeration system using phase change materials for energy-saving potentials

被引:20
|
作者
Ko, Jaedeok [1 ]
Thu, Kyaw [1 ,2 ]
Miyazaki, Takahiko [1 ,2 ]
机构
[1] Kyushu Univ, Fac Engn Sci, Dept Adv Environm Sci & Engn, Kasuga Koen 6-1, Kasuga, Fukuoka 8168580, Japan
[2] Kyushu Univ, Int Inst Carbon Neutral Energy Res I2CNER, Nishi Ku, 744 Motooka, Fukuoka, Fukuoka 8190395, Japan
关键词
R-744/R-744 cascade system; Phase change material (PCM); Compressor running time; Energy saving; Natural refrigerant; BOILING HEAT-TRANSFER; THERMODYNAMIC ANALYSIS; DISPLAY CABINET; TURBULENT PIPE; COMPRESSOR; TEMPERATURE; PERFORMANCE; FREEZERS; FLOW;
D O I
10.1016/j.applthermaleng.2020.116104
中图分类号
O414.1 [热力学];
学科分类号
摘要
A high-pressure lift often triggers an increased power input to the vapor compression systems. The increased power consumption becomes a bottleneck in R-744 refrigeration systems for freezing and refrigeration applications. Meanwhile, phase change materials (PCM) offer operation flexibility in the form of the compressor runtime from the energy storage potential. In this article, the energy-saving potential of the PCMs on a cascade refrigeration system using CO2 is investigated focusing on the impacts of charge amounts and the thermal resistance of the PCM. The validated dynamic model in Simscape (TM)/MATLAB for an R-744 vapor compression system is adopted for a cascade refrigeration system together with the validated PCM model. In the studied system, the PCM is installed in the storage compartment as a thermal buffer. The comprehensive model employed an acausal, object-oriented, and equation-based paradigm adopting detailed heat transfer characteristics. The effect of PCM on the compressor running time was investigated under the cyclic steady-state operating conditions. The results showed that the compressor "On-time" ratio decreases when using the PCM; subsequently, the power reduction. The system consumes about 6.76 kWh (without PCM) and 5.93 kWh with PCM; thus, the power consumption decreases by 12.3%. The threshold PCM charge ratio is observed to be 1. Increasing the PCM charge value above this threshold does not trigger a significant decrease in power reduction. The increase in the overall thermal resistance of PCM has a negative impact on the "On-time" ratio and power consumption. The benefit of PCM is insignificant for thermal resistance above 0.02 K W-1. Despite the shortcomings of several assumptions involved, the present results clearly highlight the positive impacts of the PCM in terms of power savings for low-temperature refrigeration applications using R-744.
引用
收藏
页数:15
相关论文
共 50 条
  • [31] Preparation and energy-saving application of polyurethane/phase change composite materials for electrical water heaters
    Hu Yougen
    Zhao Tao
    Wu Xiaolin
    Lai Maobai
    Jiang Chengming
    Sun Rong
    THIRD INTERNATIONAL CONFERENCE ON SMART MATERIALS AND NANOTECHNOLOGY IN ENGINEERING, 2012, 8409
  • [32] Cold thermal energy storage for industrial CO2 refrigeration systems using phase change material: An experimental study
    Selvnes, Hakon
    Allouche, Yosr
    Hafner, Armin
    Schlemminger, Christian
    Tolstorebrov, Ignat
    APPLIED THERMAL ENGINEERING, 2022, 212
  • [33] Experimental investigation of cascaded thermal energy storage systems using finned encapsulated phase change materials
    Jayaprakash, V
    Ganesan, S.
    Beemkumar, N.
    Kumar, M. Sunil
    Priya, K. Kamakshi
    Kaliappan, Nandagopal
    RESULTS IN ENGINEERING, 2025, 25
  • [34] Assessment of CO2 reductions and economic impacts considering energy-saving investments
    Masui, Toshihiko
    Hanaoka, Tatsuya
    Hikita, Saeko
    Kainuma, Mikiko
    ENERGY JOURNAL, 2006, : 175 - 190
  • [35] Energy-saving behavior and marginal abatement cost for household CO2 emissions
    Hamamoto, Mitsutsugu
    ENERGY POLICY, 2013, 63 : 809 - 813
  • [36] Investigation on the adaptivity of the transcritical CO2 refrigeration system with a capillary
    Song, Yulong
    Wang, Jing
    Cao, Feng
    Shu, Pengcheng
    Wang, Xiaolin
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2017, 79 : 183 - 195
  • [37] Study on the Reliability and Stability of Fatty Acid-Paraffin Ternary Phase Change Materials as Energy-saving Materials
    Shi, Yu
    Zhao, Yunchao
    Zhang, Yanmei
    Fan, Zhixuan
    Jiang, Dahua
    CHEMISTRYSELECT, 2024, 9 (10):
  • [38] Experimental and Numerical Investigation of Composite Phase Change Materials for Building Energy Saving
    Zhang, Guanhua
    Guo, Yuqian
    Liu, Zhiqiang
    Lu, Wei
    Yan, Xiaoyu
    Du, Yanping
    FRONTIERS IN ENERGY RESEARCH, 2021, 9
  • [39] INTEGRATION A ROTARY PRESSURE EXCHANGER IN TRANSCRITICAL CO2 REFRIGERATION SYSTEM: MODELING & ANNUAL ENERGY SAVING ESTIMATION
    Sarawate, Neelesh
    Deshmukh, Arnav
    Thatte, Azam
    PROCEEDINGS OF ASME TURBO EXPO 2024: TURBOMACHINERY TECHNICAL CONFERENCE AND EXPOSITION, GT2024, VOL 11, 2024,
  • [40] Integration of physical solution and ionic liquid toward efficient phase splitting for energy-saving CO2 capture
    Li, Jinyang
    Zhao, Yuzheng
    Zhan, Guoxiong
    Xing, Lei
    Huang, Zhoulan
    Chen, Zhen
    Deng, Yanxi
    Li, Junhua
    SEPARATION AND PURIFICATION TECHNOLOGY, 2024, 343