Investigation of a cascaded CO2 refrigeration system using phase change materials for energy-saving potentials

被引:20
|
作者
Ko, Jaedeok [1 ]
Thu, Kyaw [1 ,2 ]
Miyazaki, Takahiko [1 ,2 ]
机构
[1] Kyushu Univ, Fac Engn Sci, Dept Adv Environm Sci & Engn, Kasuga Koen 6-1, Kasuga, Fukuoka 8168580, Japan
[2] Kyushu Univ, Int Inst Carbon Neutral Energy Res I2CNER, Nishi Ku, 744 Motooka, Fukuoka, Fukuoka 8190395, Japan
关键词
R-744/R-744 cascade system; Phase change material (PCM); Compressor running time; Energy saving; Natural refrigerant; BOILING HEAT-TRANSFER; THERMODYNAMIC ANALYSIS; DISPLAY CABINET; TURBULENT PIPE; COMPRESSOR; TEMPERATURE; PERFORMANCE; FREEZERS; FLOW;
D O I
10.1016/j.applthermaleng.2020.116104
中图分类号
O414.1 [热力学];
学科分类号
摘要
A high-pressure lift often triggers an increased power input to the vapor compression systems. The increased power consumption becomes a bottleneck in R-744 refrigeration systems for freezing and refrigeration applications. Meanwhile, phase change materials (PCM) offer operation flexibility in the form of the compressor runtime from the energy storage potential. In this article, the energy-saving potential of the PCMs on a cascade refrigeration system using CO2 is investigated focusing on the impacts of charge amounts and the thermal resistance of the PCM. The validated dynamic model in Simscape (TM)/MATLAB for an R-744 vapor compression system is adopted for a cascade refrigeration system together with the validated PCM model. In the studied system, the PCM is installed in the storage compartment as a thermal buffer. The comprehensive model employed an acausal, object-oriented, and equation-based paradigm adopting detailed heat transfer characteristics. The effect of PCM on the compressor running time was investigated under the cyclic steady-state operating conditions. The results showed that the compressor "On-time" ratio decreases when using the PCM; subsequently, the power reduction. The system consumes about 6.76 kWh (without PCM) and 5.93 kWh with PCM; thus, the power consumption decreases by 12.3%. The threshold PCM charge ratio is observed to be 1. Increasing the PCM charge value above this threshold does not trigger a significant decrease in power reduction. The increase in the overall thermal resistance of PCM has a negative impact on the "On-time" ratio and power consumption. The benefit of PCM is insignificant for thermal resistance above 0.02 K W-1. Despite the shortcomings of several assumptions involved, the present results clearly highlight the positive impacts of the PCM in terms of power savings for low-temperature refrigeration applications using R-744.
引用
收藏
页数:15
相关论文
共 50 条
  • [1] Experimental Investigation of an Energy Saving System Using Phase Change Materials in buildings
    El-Ghetany, H. H.
    Aly, Wael I. A.
    Shalata, Hany A.
    Eid, A. I.
    Abdelwahed, Khaled
    EGYPTIAN JOURNAL OF CHEMISTRY, 2020, 63 (11): : 4533 - 4544
  • [2] Potentials and strategies for energy-saving and CO2 emission reduction in the Chinese lime industry
    Shi Wei
    Cui Yuansheng
    ZKG INTERNATIONAL, 2009, 62 (6-7): : 72 - 77
  • [3] ENERGY CONSUMPTION REDUCTION IN A REFRIGERATION SYSTEM USING PHASE CHANGE MATERIALS
    Owens, E.
    Hosseini, S. E.
    Phillips, G.
    12TH IIR/IIF INTERNATIONAL CONFERENCE ON PHASE-CHANGE MATERIALS AND SLURRIES FOR REFRIGERATION AND AIR CONDITIONING (PCM 2018), 2018, : 285 - 292
  • [4] A Review of the Energy-Saving Potential of Phase Change Material-Based Cascaded Refrigeration Systems in Chinese Food Cold Chain Industry
    Meng, Xinyu
    He, Yijian
    He, Lijuan
    Zhao, Chenlei
    Wang, Lifang
    You, Wenxi
    Zhu, Jingbo
    ENERGIES, 2024, 17 (19)
  • [5] Research on Application of Phase Change Materials in the Field of Building Energy-saving
    He, Changquan
    ADVANCED RESEARCH ON MATERIALS, APPLIED MECHANICS AND DESIGN SCIENCE, 2013, 327 : 169 - 172
  • [6] A feasible energy-saving analysis of a new system for CO2 cryogenic capture
    Li, Shuhong
    Ding, Jie
    Zhang, Xiaosong
    Cheng, Deyuan
    Hu, Xinyu
    Li, Xianliang
    INTERNATIONAL JOURNAL OF LOW-CARBON TECHNOLOGIES, 2016, 11 (02) : 235 - 239
  • [7] Energy-saving effect of a factory ceiling incorporating microencapsulated Phase Change Materials
    Lai, C-M
    PROCEEDINGS OF THE INSTITUTION OF MECHANICAL ENGINEERS PART E-JOURNAL OF PROCESS MECHANICAL ENGINEERING, 2012, 226 (E2) : 174 - 177
  • [8] Feasibility study on an energy-saving desiccant wheel system with CO2 heat pump
    Liu, Yefeng
    Meng, Deren
    Chen, Shen
    INTERNATIONAL CONFERENCE ON ENERGY ENGINEERING AND ENVIRONMENTAL PROTECTION (EEEP2017), 2018, 121
  • [9] Experimental Investigation and Energy-saving Analysis of a CO2 Thermosyphon for Free Cooling of Data Centers
    Zhang, Hai-Nan
    Shao, Shuang-Quan
    Tian, Chang-Qing
    Jin, Ting-Xiang
    Kung Cheng Je Wu Li Hsueh Pao/Journal of Engineering Thermophysics, 2017, 38 (09): : 1833 - 1836
  • [10] Performance Investigation of Cascade Refrigeration System Using CO2 and Mixtures
    Jemni, Nourheine
    Elakhdar, Mouna
    Nehdi, Ezzedine
    Kairouani, Lakdar
    INTERNATIONAL JOURNAL OF AIR-CONDITIONING AND REFRIGERATION, 2015, 23 (03)