Influence of Design Parameters and Defects on Electric Field Distributions inside MV Cable Joints

被引:0
|
作者
Metwally, I. A. [1 ]
Al-Badi, A. H. [1 ]
Al-Hinai, A. S. [1 ]
Al Kamali, F. [1 ]
AI-Ghaithi, H. [1 ]
机构
[1] Sultan Qaboos Univ, Coll Engn, Dept Elect & Comp Engn, Muscat, Oman
来源
PROCEEDINGS OF THE 18TH MEDITERRANEAN ELECTROTECHNICAL CONFERENCE MELECON 2016 | 2016年
关键词
cable joints; electric field distribution; defects; failure; finite element method;
D O I
暂无
中图分类号
TP39 [计算机的应用];
学科分类号
081203 ; 0835 ;
摘要
This paper presents a 2d finite-element analysis for a 33-kV, three-phase, three-core cross-linked polyethylene (XLPE) underground cable (UGC) straight joint of the heat shrink type. The aim of this work is to show how the joint design parameters and different defects affect the electric field distribution, and find optimum material properties to enhance the lifetime of cable joints. This is investigated by calculating the electric field distributions and showing how the optimized selection of joint material properties can reduce the localized high electric field to avoid partial discharge activities. Several design parameters are investigated such as insulation layer's thickness and relative permittivity, and termination angles of ferrule and its insulation. In addition, size and location of different defects such as air voids, water droplets, sharp tips and delamination are examined. The paper concludes important points for proper design of medium-voltage (MV) cable joints to enhance their lifetime and hence increase the reliability of such cable systems.
引用
收藏
页数:6
相关论文
共 24 条
  • [21] Parameters design optimization of 230 kV corona ring based on electric field analysis and response surface methodology
    Terrab, Hocine
    Kara, Adel
    ELECTRIC POWER SYSTEMS RESEARCH, 2018, 163 : 782 - 788
  • [22] Finite element analysis of electric field distribution in water treed XLPE cable insulation (1): The influence of geometrical configuration of water electrode for accelerated water treeing test
    Kim, Chonung
    Jang, Jongbok
    Huang, Xingyi
    Jiang, Pingkai
    Kim, Hyeil
    POLYMER TESTING, 2007, 26 (04) : 482 - 488
  • [23] Influence of Design and Process Parameters of 32-nm Advanced-Process High-kp-MOSFETs on Negative-Bias Temperature Instability and Study of Defects
    A. F. Muhammad Alimin
    A. A. Mohd Radzi
    N. A. F. Sazali
    S. F. Wan Muhamad Hatta
    N. Soin
    H. Hussin
    Journal of Electronic Materials, 2017, 46 : 5942 - 5949
  • [24] Influence of Design and Process Parameters of 32-nm Advanced-Process High-k p-MOSFETs on Negative-Bias Temperature Instability and Study of Defects
    Alimin, A. F. Muhammad
    Radzi, A. A. Mohd
    Sazali, N. A. F.
    Hatta, S. F. Wan Muhamad
    Soin, N.
    Hussin, H.
    JOURNAL OF ELECTRONIC MATERIALS, 2017, 46 (10) : 5942 - 5949