Surface Charge Accumulation on 500kV Cone-Type GIS Spacer under Residual DC Voltage

被引:18
|
作者
Zhou, Hong-yang [1 ]
Ma, Guo-ming [1 ]
Wang, Yuan [1 ]
Li, Cheng-rong [1 ]
Tu, You-Ping [1 ]
Ye, San-pai [2 ]
Zhang, Bo [2 ]
Guo, Xue-feng [2 ]
Yan, Xiang-lian [3 ]
机构
[1] North China Elect Power Univ, Beijing Key Lab High Voltage & EMC, Key Lab Alternate Elect Power Syst Renewable Ener, Beinong Rd 2, Beijing 102206, Peoples R China
[2] Pinggao Grp Co Ltd, Pingdingshan 467001, Peoples R China
[3] China Elect Power Res Inst, High Voltage Res Dept, 15 Xiaoying East Rd, Beijing 100192, Peoples R China
关键词
DC residual voltage; 500 kV cone-type spacer; surface charge accumulation; flashover test; ELECTRIC CHARGES; SF6; GAS; INSULATORS; SYSTEMS;
D O I
10.1109/TDEI.2018.007144
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In recent years, GIS compact design has gradually been recognized and adopted by the industry. In the trend of the compact design, the insulation performance of the cone-type spacer is getting more and more attention by GIS manufacturers and grid operators and maintenance departments. In particular, under the action of DC residual pressure, the insulation properties of cone-type spacer become the focus of attention of all parties. Based on the field equipment operating conditions, the experimental study of DC residual voltage for the true cone-type spacer insulation performance is significant. In order to obtain the proposed pre-stressed time of DC voltage and distributions of surface charge, for the insulation test of 500 kV cone-type spacer under lightning impulse with DC voltage superimposed. A full scale surface charge measurement platform is build up for 500 kV GIS spacer. Then, long-term DC voltage experiments were carried out to obtain the distributions of surface charge on spacer in stationary state under different voltages. Moreover, the saturation time of surface charge accumulation under different DC electric stress is calculated and discussed. The study results show that (1) the distribution of surface charge on spacer is not uniform. It can be observed that on most areas of 500 kV spacer concave surface is dominated by the electric conduction through the volume with positive charges. (2) The time constant of surface charge accumulation decreases with the residual DC voltage amplitude, it can be estimated that the saturation time of surface charge accumulation on 500 kV cone-type spacer is about 23 h for the residual DC voltage reach to 1.0 p.u. The study results are thought to be helpful to the insulation test of 500 kV cone-type spacer under impulse voltage with a superimposed residual DC voltage.
引用
收藏
页码:1230 / 1237
页数:8
相关论文
共 12 条
  • [1] Temperature Dependence of Surface Charge Accumulation on DC-GIS Insulating Spacer
    Shimakawa, Hajime
    Sato, Masahiro
    Kumada, Akiko
    Hidaka, Kunihiko
    Yasuoka, Takanori
    Hoshina, Yoshikazu
    Shiiki, Motoharu
    IEEE TRANSACTIONS ON POWER DELIVERY, 2022, 37 (06) : 4539 - 4547
  • [2] Surface Charge Accumulation on Silicon Rubber Material under DC Voltage in Atmosphere
    Su, Guo-Qiang
    Mu, Hai-Bao
    Shen, Wen-Wei
    Song, Bai-Peng
    Lang, Yan
    Zhang, Guan-Jun
    2013 IEEE CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA (CEIDP), 2013, : 456 - 459
  • [3] Surface charge distribution patterns of a truncated cone-type spacer for high-voltage direct current gas-insulated metal-enclosed transmission line/gas-insulated metal-enclosed switchgear
    Xue, Jianyi
    Wang, Han
    Liu, Yanqin
    Li, Kefeng
    Liu, Xiangyu
    Fan, Xiaofeng
    Deng, Junbo
    Zhang, Guanjun
    Guo, Baohong
    IET SCIENCE MEASUREMENT & TECHNOLOGY, 2018, 12 (04) : 436 - 442
  • [4] Surface Charge Accumulation on a Real Size Epoxy Insulator With Bouncing Metal Particle Under DC Voltage
    Gao, Yu
    Wang, Huan
    Yuan, Xiaochen
    Zhao, Huicun
    Li, Ziyi
    IEEE TRANSACTIONS ON PLASMA SCIENCE, 2021, 49 (07) : 2166 - 2175
  • [5] Influence of Temperature and Positive Voltage on Surface Charge Accumulation for the Disc Insulator of GIL Under DC Voltage
    Yan W.
    Zhang Z.
    Deng B.
    Zhang Z.
    Gaodianya Jishu/High Voltage Engineering, 2019, 45 (12): : 3889 - 3897
  • [6] Metal nanoparticle-doped epoxy resin to suppress surface charge accumulation on insulators under DC voltage
    Wang, Tian-Yu
    Zhang, Bo-Ya
    Li, Da-Yu
    Hou, Yi-Cen
    Zhang, Gui-Xin
    NANOTECHNOLOGY, 2020, 31 (32)
  • [7] Effect of Insulation Distance on Surface Charge Accumulation at the Gas-Solid Interface Under DC Voltage
    Han, Pu
    Pan, Cheng
    Pan, Zijun
    Ye, Yuhan
    Qiu, Yujie
    Mao, Shiyi
    Tang, Ju
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2024, 31 (06) : 3140 - 3149
  • [8] Metal particle encouraged surface charge accumulation on epoxy insulator with multi-arc surface profile under DC voltage
    Gao, Yu
    Li, Ziyi
    Wang, Huan
    Yuan, Xiaochen
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2020, 27 (03) : 998 - 1006
  • [9] Surface charge accumulation and pre-flashover characteristics induced by metal particles on the insulator surfaces of 1100 kV GILs under AC voltage
    Li Xing
    Liu Weidong
    Xu Yuan
    Chen Weijiang
    Bi Jiangang
    HIGH VOLTAGE, 2020, 5 (02) : 134 - 142
  • [10] Study on Surface Charge Accumulation Characteristics of Resin Impregnated Paper Wall Bushing Core Under Positive DC Voltage
    Chen, Ming
    Liu, Xuandong
    Liang, Chengjun
    Zhao, Yi
    Tang, Hao
    ENERGIES, 2019, 12 (23)