Study on optimal ice storage capacity of ice thermal storage system and its influence factors

被引:61
作者
Song, Xu [1 ]
Zhu, Tong [1 ]
Liu, Liuchen [1 ]
Cao, Zhenjun [2 ]
机构
[1] Tongji Univ, Sch Mech & Energy Engn, Shanghai 201804, Peoples R China
[2] Shanghai Zhixin Elect Co Ltd, Shanghai 200080, Peoples R China
关键词
Ice thermal storage; Chiller priority; Storage priority; Optimal control; Optimal ice storage capacity; ENERGY-STORAGE; COMMERCIAL BUILDINGS; CHONGMING COUNTY; COOLING SYSTEM; OPTIMIZATION; PLANTS; MASS;
D O I
10.1016/j.enconman.2018.03.007
中图分类号
O414.1 [热力学];
学科分类号
摘要
This paper explores the impact of different control strategies and electric tariff structures on the optimal ice storage capacity in relation to system economy for four typical buildings of hotel, restaurant, mall and office. The ice storage rate and electric price ratio are introduced to denote the various ice storage capacities and the different electric tariff structures, respectively. Then the chiller capacity and economic evaluation index value corresponding to each typical building with various ice storage rates and electric price ratios under three control strategies (chiller priority, storage priority, and optimizing) are calculated. The results indicated that there is respective optimal ice storage rate corresponding to both the minimal chiller capacity and the minimal economic evaluation index value. The optimal ice storage rate in relation to minimal chiller capacity is constant value under each control strategy. Such optimal values under both chiller priority and optimized control strategies are equivalent and less than that under storage priority control strategy. However, the optimal ice storage rate in relation to minimal economic evaluation index value under each control strategy is significantly affected by the electric tariff structures. The corresponding optimal ice storage rates under both chiller priority and optimized control strategies are equivalent and increase to a definite value with the increase in the electric price ratio. While the optimal ice storage rate under storage priority control strategy will appear when electric price ratio is greater than 3. The results also showed that, when electric price ratio increases to a certain value, the optimal ice storage rates corresponding to both minimal economic expense and minimal chiller capacity under each control strategy for the four typical buildings are equivalent.
引用
收藏
页码:288 / 300
页数:13
相关论文
共 50 条
[21]   Experimental study of ice storage performance in an office building [J].
Schibuola, L .
INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 1998, 22 (08) :751-759
[22]   Numerical study of thin layer ring on improving the ice formation of building thermal storage system [J].
Xie, Junling ;
Yuan, Chris .
APPLIED THERMAL ENGINEERING, 2014, 69 (1-2) :46-54
[23]   An Optimal Integrated Approach to Design and Operate Ice Thermal Storage for Typical HVAC Systems [J].
Nassif, Nabil ;
AlRifaie, Fouad ;
AlRaees, Nihal .
2018 ASHRAE WINTER CONFERENCE, 2018,
[24]   Study on continuous ice slurry formation using functional fluid for ice storage - Discussion of optimal operating conditions [J].
Matsumoto, Koji ;
Suzuki, Yutaka ;
Okada, Masashi ;
Teraoka, Yoshikazu ;
Kawagoe, Tetsuo .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2006, 29 (07) :1208-1217
[25]   NUMERICAL STUDY OF FACTORIAL IMPACT OF THIN LAYER RING ON IMPROVING THERMAL PERFORMANCE OF ICE THERMAL STORAGE SYSTEM [J].
Xie, Junling ;
Yuan, Chris .
PROCEEDINGS OF THE ASME 10TH INTERNATIONAL MANUFACTURING SCIENCE AND ENGINEERING CONFERENCE, 2015, VOL 2, 2015,
[26]   Optimal control of building storage systems using both ice storage and thermal mass - Part I: Simulation environment [J].
Hajiah, Ali ;
Krarti, Moncef .
ENERGY CONVERSION AND MANAGEMENT, 2012, 64 :499-508
[27]   Optimal controls of building storage systems using both ice storage and thermal mass - Part II: Parametric analysis [J].
Hajiah, Ali ;
Krarti, Moncef .
ENERGY CONVERSION AND MANAGEMENT, 2012, 64 :509-515
[28]   Performance analysis on the liquid-ice thermal storage system for optimum operation [J].
Yamada, M ;
Fukusako, S ;
Kawanami, T .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2002, 25 (02) :267-277
[29]   Experimental and numerical study of thin ring and annular fin effects on improving the ice formation in ice-on-coil thermal storage systems [J].
Jannesari, Hamid ;
Abdollahi, Naeim .
APPLIED ENERGY, 2017, 189 :369-384
[30]   Study on the Optimization of Multi-factor Influencing Ice Thermal Storage Air Conditioning System Economy [J].
Wang, Zhiwei ;
Yang, Qiuli ;
Zhang, Leimin ;
Han, Liping ;
Sun, Jie .
MANUFACTURING SCIENCE AND MATERIALS ENGINEERING, PTS 1 AND 2, 2012, 443-444 :333-+