Partial Discharge Analysis of SF6/N2 Gas Mixture Filled MV Circuit Breaker Using Time-Frequency Map Clustering Technique

被引:0
|
作者
Yuvaraj, R. [1 ]
Chandrasekar, S. [2 ]
机构
[1] Gnanamani Coll Technol, Dept Elect & Elect Engn, Namakkal, India
[2] Sona Coll Technol, Dept Elect & Elect Engn, SonaPERT R&D Ctr, Salem 636005, India
关键词
Circuit breaker; Partial discharge; Gas insulation; Time– frequency map; Clustering technique; SF6; SYSTEMS;
D O I
10.1007/s42835-020-00597-1
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Breakdown of gas insulated switchgears due to partial discharges (PD) is a major threat for the safe and reliable operation of power system network. In recent times, PD based diagnostics has been widely adopted by electrical utilities in order to evaluate the health of high voltage insulation system. However, very few reports are only available on the PD characteristics of gas insulated medium voltage (MV) circuit breaker prototypes, in particular with mixture of gases, over a wide range of pressure and voltage stress. Deep analysis of nature of PD signals in mixture of gas insulation and its time-frequency characteristics is important in order to develop efficient online condition monitoring systems for circuit breakers. This paper is aimed at the analysis of PD characteristics of a 22 kV MV circuit breaker prototype filled with SF6/N-2 gas mixtures using time-frequency (T-F) mapping and clustering technique. PD tests are carried out at different gas pressures (1-5 bar) and at different gas mixture ratios. Important PD parameters such as PD inception voltage, phase resolved PD (PRPD) pattern and PD repetition rate are evaluated. Clustering analysis of PD signals from the time-frequency mapping is carried out and formation of three different clusters consisting of short, long and repetitive PD pulses is identified. Online real time monitoring of individual cluster density will be helpful to understand the degradation of gas insulation of circuit breakers. Keeping in mind the minimal usage of SF6 gas, from the results, it is noted that 10% SF6 gas can be mixed with 90% N-2 at 3 bar pressure to get satisfactory PD performance of a 22 kV medium voltage circuit breaker.
引用
收藏
页码:499 / 507
页数:9
相关论文
共 50 条
  • [21] SF6 gas recovery from SF6/N2 mixtures using polymer membrane
    Yamamoto, O
    Takuma, T
    Kawamura, A
    Hashimoto, K
    Hatano, N
    Kinouchi, M
    GASEOUS DIELECTRICS IX, 2001, : 555 - 560
  • [22] The calculation of arc conductance in SF6-N2 mixture gas circuit breaker
    Oh, Yeon-Ho
    Song, Ki-Dong
    2015 3RD INTERNATIONAL CONFERENCE ON ELECTRIC POWER EQUIPMENT - SWITCHING TECHNOLOGY (ICEPE-ST), 2015, : 359 - 362
  • [23] Decomposition Characteristics of SF6/N2 Under Partial Discharge of Different Degrees
    Li, Chen
    Tang, Ju
    Zhao, Zhiqiang
    Li, Haotian
    Miao, Yulong
    Zeng, Fuping
    IEEE ACCESS, 2020, 8 : 192312 - 192319
  • [24] Partial Discharge Characteristics of SF6 and SF6/N2 in Nonuniform Electric Field Under Negative DC Voltage
    Han, Xutao
    Zhang, Xuanrui
    Wang, Haotian
    Sun, Yuan
    Zhou, Yang
    Li, Junhao
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2023, 30 (01) : 131 - 138
  • [25] Synergistic effect of SF6/N2 gas mixtures on surface partial discharge under DC voltage
    Hou, Zhiqiang
    Guo, Ruochen
    He, Cong
    Li, Junhao
    Yao, Xiu
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2020, 27 (02) : 692 - 699
  • [26] Partial discharge and breakdown mechanisms in ultra-dilute SF6 and PFC gases with N2 gas
    Yamada, T
    Ishida, T
    Hayakawa, N
    Yuasa, S
    Okabe, S
    Okubo, H
    GASEOUS DIELECTRICS IX, 2001, : 239 - 244
  • [27] Metallic Particle Behavior in a Gas Insulated Busduct with SF6/N2 Gas Mixture
    Rao, M. R.
    Amarnath, J.
    2011 14TH INTERNATIONAL SYMPOSIUM ON ELECTRETS (ISE), 2011, : 197 - +
  • [28] Effect of Gas-Mixture Ratio on the Characteristics of Positive DC Corona Discharge in SF6/N2 Gas Mixtures
    He, Yanliang
    Ding, Wei
    Sun, Anbang
    Zhang, Guanjun
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2021, 28 (03) : 829 - 837
  • [29] Research on the synergy of SF6/N2 mixture gas in low temperature environment
    Wang, Y.
    Liang, J. Q.
    Yu, C. L.
    Li, L.
    Zhang, H. D.
    Li, G. X.
    3RD INTERNATIONAL CONFERENCE ON NEW MATERIAL AND CHEMICAL INDUSTRY, 2019, 479
  • [30] Non intrusive method for the assessment of SF6/N2 gas mixture ratio
    Dupraz, JP
    Montillet, GF
    2003 IEEE PES TRANSMISSION AND DISTRIBUTION CONFERENCE & EXPOSITION, VOLS 1-3, CONFERENCE PROCEEDINGS: BLAZING TRAILS IN ENERGY DELIVERY AND SERVICES, 2003, : 786 - 791