Feedforward Current References Control for DFIG-Based Wind Turbine to Improve Transient Control Performance During Grid Faults

被引:93
作者
Zhu, Donghai [1 ]
Zou, Xudong [1 ]
Zhou, Shiying [1 ]
Dong, Wen [1 ]
Kang, Yong [1 ]
Hu, Jiabing [1 ]
机构
[1] Huazhong Univ Sci & Technol, Sch Elect & Elect Engn, State Key Lab Adv Electromagnet Engn & Technol, Wuhan 430074, Hubei, Peoples R China
基金
国家重点研发计划;
关键词
AC current references; doubly fed induction generator (DFIG); feedforward current references control (FCRC); low-voltage ride through (LVRT); references tracking; FED INDUCTION GENERATOR; RIDE-THROUGH; SYSTEMS; DYNAMICS; TRACKING; FRAME;
D O I
10.1109/TEC.2017.2779864
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
For doubly fed induction generator (DFIG) based wind turbines, when severe grid faults occur, it is necessary to inject transient and negative-sequence components into the rotor current reference to achieve controllable low-voltage ride through (LVRT) capability. However, the classical proportional-integral (PI) controller cannot provide precise control of the transient and negative-sequence rotor current, because such current references in synchronous reference frame (SRF) are ac components at grid frequency and double grid frequency, respectively. To solve this problem, this paper proposes a feedforward current references control (FCRC) method for rotor-side converter to improve the system transient control performance. Under the proposed method, the additional feedforward of rotor current references is introduced into the current loop to improve its tracking capability of the aforementioned ac current references, thereby achieving the transient control targets precisely. Moreover, the proposed method will not affect the stability of the original current loop. Furthermore, the method has strong robustness against DFIG parameters deviation and grid frequency variations. In addition, the method is highly simple to implement. Finally, the validity of the proposed FCRC method is demonstrated by simulation and experiment.
引用
收藏
页码:670 / 681
页数:12
相关论文
共 43 条
[1]   Robust Controller for DFIGs of Grid-Connected Wind Turbines [J].
da Costa, Jean Patric ;
Pinheiro, Humberto ;
Degner, Thomas ;
Arnold, Gunter .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2011, 58 (09) :4023-4038
[2]   Nonlinear inversion-based output tracking [J].
Devasia, S ;
Chen, DG ;
Paden, B .
IEEE TRANSACTIONS ON AUTOMATIC CONTROL, 1996, 41 (07) :930-942
[3]   Should model-based inverse inputs be used as feedforward under plant uncertainty? [J].
Dëvasia, S .
IEEE TRANSACTIONS ON AUTOMATIC CONTROL, 2002, 47 (11) :1865-1871
[4]  
Erickson R., 2007, Fundamentals of power electronics
[5]   Unbalanced Voltage Sag Ride-Through of a Doubly Fed Induction Generator Wind Turbine With Series Grid-Side Converter [J].
Flannery, Patrick S. ;
Venkataramanan, Giri .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2009, 45 (05) :1879-1887
[6]   LVRT Capability of DFIG-Based WECS Under Asymmetrical Grid Fault Condition [J].
Geng, Hua ;
Liu, Cong ;
Yang, Geng .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2013, 60 (06) :2495-2509
[7]   Modeling of DFIG-Based WTs for Small-Signal Stability Analysis in DVC Timescale in Power Electronized Power Systems [J].
Hu, Jiabing ;
Yuan, Hao ;
Yuan, Xiaoming .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 2017, 32 (03) :1151-1165
[8]   Small Signal Dynamics of DFIG-Based Wind Turbines During Riding Through Symmetrical Faults in Weak AC Grid [J].
Hu, Jiabing ;
Wang, Bo ;
Wang, Weisheng ;
Tang, Haiyan ;
Chi, Yongning ;
Hu, Qi .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 2017, 32 (02) :720-730
[9]   Small Signal Instability of PLL-Synchronized Type-4 Wind Turbines Connected to High-Impedance AC Grid During LVRT [J].
Hu, Jiabing ;
Hu, Qi ;
Wang, Bo ;
Tang, Haiyan ;
Chi, Yongning .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 2016, 31 (04) :1676-1687
[10]   Improved Control of DFIG Systems During Network Unbalance Using PI-R Current Regulators [J].
Hu, Jiabing ;
He, Yikang ;
Xu, Lie ;
Williams, Barry W. .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2009, 56 (02) :439-451