Analysis of combined cooling, heating, and power systems under a compromised electric-thermal load strategy

被引:39
作者
Han, Gang [1 ]
You, Shijun [1 ,2 ]
Ye, Tianzhen [1 ]
Sun, Peng [1 ]
Zhang, Huan [1 ,2 ]
机构
[1] Tianjin Univ, Sch Environm & Equipment Engn, Tianjin 300072, Peoples R China
[2] Tianjin Univ, Sch Environm & Equipment Engn, Key Lab Efficient Utilizat Low & Medium Grade Ene, MOE, Tianjin 300072, Peoples R China
关键词
CCHP systems; Evaluation criteria; Efficacy coefficient method; Compromised electric-thermal load strategy; TRIGENERATION SYSTEM; PERFORMANCE ANALYSIS; CCHP; OPTIMIZATION; ENERGY;
D O I
10.1016/j.enbuild.2014.09.006
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Following the electric load (FE) and following the thermal load (FT) strategies both have advantages and disadvantages for combined cooling, heating and power (CCHP) systems. In this paper, the performance of different strategies is evaluated under operation cost (CC), carbon dioxide emission (CDE) and exergy efficiency (EE). Analysis of different loads in one hour is conducted under the assumption that the additional electricity is not allowed to be sold back to the grid. The results show that FE produces less CC, less CDE, and FT produces higher EE when the electric load is larger. However, FE produces less CC, less CDE and higher EE when the thermal load is larger. Based on a hybrid electric-thermal load (HET) strategy, compromised electric-thermal (CET) strategies are innovatively proposed using the efficacy coefficient method. Additional, the CCHP system of a hotel in Tianjin is analyzed for all of the strategies. The results for an entire year indicate the first CET strategy is the optimal one when dealing with CC, CDE and EE. And the second CET is the optimal one when dealing with CC and EE. Moreover, the laws are strictly correct for different buildings in qualitative terms. (C) 2014 Elsevier B.V. All rights reserved.
引用
收藏
页码:586 / 594
页数:9
相关论文
共 24 条
[1]   Application of the multi-objective optimization and risk analysis for the sizing of a residential small-scale CCHP system [J].
Abdollahi, Hoseyn Sayyaadi Gholamhossein .
ENERGY AND BUILDINGS, 2013, 60 :330-344
[2]   Economic and environmental based operation strategies of a hybrid photovoltaic-microgas turbine trigeneration system [J].
Basrawi, Firdaus ;
Yamada, Takanobu ;
Obara, Shin'ya .
APPLIED ENERGY, 2014, 121 :174-183
[3]   Theoretical analysis of performance of a micro gas turbine co/trigeneration system for residential buildings in a tropical region [J].
Basrawi, Firdaus ;
Yamada, Takanobu ;
Obara, Shin'ya .
ENERGY AND BUILDINGS, 2013, 67 :108-117
[4]   High resolution performance analysis of micro-trigeneration in an energy-efficient residential building [J].
Borg, Simon Paul ;
Kelly, Nicolas James .
ENERGY AND BUILDINGS, 2013, 67 :153-165
[5]  
Cardona E., 2006, J ENERGY RESOURCES T, V126, P490
[6]  
Dincer I., 2007, ENV SUSTAINABLE DEV
[7]   An energy and exergy analysis of a high-efficiency engine trigeneration system for a hospital: A case study methodology based on annual energy demand profiles [J].
do Espirito Santo, Denilson Boschiero .
ENERGY AND BUILDINGS, 2014, 76 :185-198
[8]   Prime mover selection for a residential micro-CCHP by using two multi-criteria decision-making methods [J].
Ebrahimi, Masood ;
Keshavarz, Ali .
ENERGY AND BUILDINGS, 2012, 55 :322-331
[9]   Optimization of CHCP (combined heat power and cooling) systems operation strategy using dynamic programming [J].
Facci, Andrea Luigi ;
Andreassi, Luca ;
Ubertini, Stefano .
ENERGY, 2014, 66 :387-400
[10]   Analysis of combined cooling, heating, and power systems based on source primary energy consumption [J].
Fumo, Nelson ;
Chamra, Louay M. .