Piping Fragility Evaluation: Interaction With High-Rise Building Performance

被引:9
作者
Ju, Bu Seog [1 ]
Gupta, Abhinav [1 ]
Ryu, Yong Hee [1 ]
机构
[1] North Carolina State Univ, Dept Civil Engn, Raleigh, NC 27695 USA
来源
JOURNAL OF PRESSURE VESSEL TECHNOLOGY-TRANSACTIONS OF THE ASME | 2017年 / 139卷 / 03期
基金
美国国家科学基金会;
关键词
piping fragility; threaded Tee-joint performance; building-piping interaction; first-leakage limit state; SEISMIC FRAGILITY; SYSTEMS; DESIGN;
D O I
10.1115/1.4034406
中图分类号
TH [机械、仪表工业];
学科分类号
0802 ;
摘要
Many recent studies have emphasized the need for improving seismic performance of nonstructural systems in critical facilities in order to reduce the damage as well as to maintain continued operation of the facility after an earthquake. This paper is focused on evaluating system-level seismic fragility of the piping in a representative high-rise building. Piping fragilities are evaluated by incorporating the nonlinear finite-element model of a threaded Tee-joint that is validated using experimental results. The emphasis in this study is on evaluating the effects of building performance on the piping fragility. The differences in piping fragility due to the nonlinearities in building are evaluated by comparing the fragility curves for linear frame and nonlinear fiber models. It is observed that as nonlinearity in the building increases with increasing value of peak ground acceleration, the floor accelerations exhibit a reduction due to degradation/softening. Consequently, the probabilities of failure increase at a slower rate relative to that in a linear frame. It is also observed that a piping located at higher floor does not necessarily exhibits high fragilities, i. e., the fundamental building mode is not always the governing mode. Higher order building modes with frequencies closest to critical piping modes of interest contribute more significantly to the piping fragility. Within a particular building mode of interest, a good indicator of the amplification at different floor levels can be obtained by the product of mode shape ordinate and modal participation factor. Piping fragilities are likely to be higher at floor levels at which this product has a higher value.
引用
收藏
页数:10
相关论文
共 27 条
[1]  
[Anonymous], 1997, UN BUILD COD
[2]  
[Anonymous], NFPA13
[3]  
[Anonymous], 2006, PEER CENT
[4]  
ASME, 2004, RUL CONSTR NUCL FAC
[5]   Seismic analysis of high-rise mega-braced frame-core buildings [J].
Brunesi, E. ;
Nascimbene, R. ;
Casagrande, L. .
ENGINEERING STRUCTURES, 2016, 115 :1-17
[6]  
Dey A, 1999, EARTHQUAKE ENG STRUC, V28, P351
[7]  
Dow J., 2010, Testing and Analysis of Iron and Plastic T-joint in Sprinkler Systems," NEESRGC: "Simulation of the Seismic Performance of Nonstructural Systems"
[8]  
Englekirk R.E., 2003, SEISMIC DESIGN REINF
[9]   Seismic analysis of the world's tallest building [J].
Fan, Hong ;
Li, Q. S. ;
Tuan, Alex Y. ;
Xu, Lihua .
JOURNAL OF CONSTRUCTIONAL STEEL RESEARCH, 2009, 65 (05) :1206-1215
[10]   Performance-based seismic design of nonstructural building components: The next frontier of earthquake engineering [J].
Filiatrault, Andre ;
Sullivan, Timothy .
EARTHQUAKE ENGINEERING AND ENGINEERING VIBRATION, 2014, 13 :17-46