Subsynchronous oscillation and its mitigation of VSC-MTDC with doubly-fed induction generator-based wind farm integration

被引:6
作者
Su, Miaohong [1 ]
Dong, Haiying [1 ,2 ]
Liu, Kaiqi [1 ]
Zou, Weiwei [1 ]
机构
[1] Lanzhou Jiaotong Univ, Sch Automat & Elect Engn, Lanzhou, Peoples R China
[2] Lanzhou Jiaotong Univ, Sch New Energy & Power Engn, Lanzhou, Peoples R China
关键词
doubly-fed induction generator; eigenvalue analysis; multi-channel variable-parameter subsynchronous damping controller; subsynchronous oscillation voltage source converter based multi-terminal direct current transmission system; STABILITY ANALYSIS;
D O I
10.24425/aee.2021.136052
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Wind power integration through the voltage source converter-based high-voltage direct current (VSC-HVDC) system will be a potential solution for delivering large-scale wind power to the "Three-North Regions" of China. However, the interaction between the doubly-fed induction generator (DFIG) and VSC-HVDC system may cause the risk of subsynchronous oscillation (SSO). This paper establishes a small-signal model of the VSC based multi-terminal direct current (VSC-MTDC) system with new energy access for the problem, and the influencing factors causing SSO are analyzed based on the eigenvalue analysis method. The theoretical analysis results show that the SSO in the system is related to the wind farm operating conditions, the rotor-side controller (RSC) of the DFIG and the interaction of the controller in the VSC-MTDC system. Then, the phase lag characteristic is obtained based on the signal test method, and a multi-channel variable-parameter subsynchronous damping controller (SSDC) is designed via selecting reasonable parameters. Finally, the correctness of the theoretical analysis and the effectiveness of the multi-channel variable-parameter SSDC are verified based on time-domain simulation.
引用
收藏
页码:53 / 72
页数:20
相关论文
共 26 条
[1]   Understanding the Origin of Oscillatory Phenomena Observed Between Wind Farms and HVdc Systems [J].
Amin, Mohammad ;
Molinas, Marta .
IEEE JOURNAL OF EMERGING AND SELECTED TOPICS IN POWER ELECTRONICS, 2017, 5 (01) :378-392
[2]  
[边晓燕 Bian Xiaoyan], 2018, [电力系统自动化, Automation of Electric Power Systems], V42, P25
[3]  
Chen B.P, 2018, ARXIV181103728
[4]  
Chen C, 2018, SO POWER SYSTEM TECH, V12, P84
[5]  
Gao Ben-feng, 2010, High Voltage Engineering, V36, P501
[6]  
Guo X.S., 2020, P CSEE, V40
[7]  
Jiang P., 2011, ELECT POWER AUTOMATI, V31, P27
[8]  
[姜齐荣 Jiang Qirong], 2017, [高电压技术, High Voltage Engineering], V43, P1057
[9]  
Jing He, 2012, Combinatorial Optimization and Applications. Proceedings 6th International Conference, COCOA 2012, P1, DOI 10.1007/978-3-642-31770-5_1
[10]   Small-Signal Stability Analysis of Multi-Terminal VSC-Based DC Transmission Systems [J].
Kalcon, Giddani O. ;
Adam, Grain P. ;
Anaya-Lara, Olimpo ;
Lo, Stephen ;
Uhlen, Kjetil .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2012, 27 (04) :1818-1830