Study on pollution flashover characteristic of insulators on 500kV AC transmission lines in high-altitude area

被引:1
作者
Huang, Ruiping [1 ]
Zhou, Jun [1 ]
Xu, Yueneng [1 ]
机构
[1] China Elect Power Res Inst, 15 Xiaoying Rd, Beijing 100192, Peoples R China
来源
JOURNAL OF ENGINEERING-JOE | 2019年 / 16期
关键词
flashover; power transmission lines; insulator testing; insulation; external insulation; Tibet high-altitude test base; Beijing UHVDC test base; flashover voltages; AC transmission line project; pollution flashover characteristics; artificial pollution testing; equivalent salt deposit density; voltage; 500; 0; kV; PERFORMANCE;
D O I
10.1049/joe.2018.8468
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
Pollution flashover performance of insulators is one of the key factors to be considered in the selection of external insulation for transmission lines at high-altitude areas. In pollution laboratories at Tibet high-altitude test base and Beijing ultra high voltage direct current (UHVDC) test base, artificial pollution tests of insulators adopted in AC 500kV transmission project are performed both in sea-level region and real high-altitude regions, through which flashover voltages at typical equivalent salt deposit density are obtained. The relationship between altitude and flashover voltage is acquired as well.
引用
收藏
页码:3306 / 3309
页数:4
相关论文
共 12 条