Estimation of the minimum shielding failure flashover current for first and subsequent lightning strokes to overhead transmission lines

被引:36
作者
Datsios, Zacharias G. [1 ]
Mikropoulos, Pantelis N. [1 ]
Tsovilis, Thomas E. [1 ]
机构
[1] Aristotle Univ Thessaloniki, Fac Engn, Sch Elect & Comp Engn, High Voltage Lab, Thessaloniki 54124, Greece
关键词
ATP-EMTP; Insulation coordination; Insulator string flashover; Overhead transmission lines; Shielding failure; VOLT-TIME CHARACTERISTICS; AIR GAPS; PERFORMANCE; TESTS; MODEL;
D O I
10.1016/j.epsr.2014.03.008
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
ATP-EMTP simulations are performed to estimate the minimum shielding failure current causing flashover in overhead transmission lines with operating voltage in the range of 66 kV up to 735 kV. This critical current, affecting shielding failure flashover rate, is of great importance for assessing the insulation coordination of overhead transmission lines and the connected substations. The minimum shielding failure current causing flashover of line insulation is highly dependent upon insulator string flashover modelling and, also, markedly higher than that calculated according to the relevant IEEE Std 1243-1997 simplified expression. A modification of the latter is suggested by using multiplication factors of 1.5 and 1.65 for first and subsequent lightning strokes, respectively, so as to account for the increased dielectric strength of line insulator strings under non-standard lightning overvoltage surges. Alternatively, the critical currents can be respectively estimated by using average negative breakdown gradients per unit length of insulator string of 680 kV/m and 750 kV/m. The shielding failure flashover rate of the overhead transmission lines, being greatly influenced by insulator string flashover modelling, is lower than that obtained based on the critical current according to IEEE Std 1243-1997. (C) 2014 Elsevier B.V. All rights reserved.
引用
收藏
页码:141 / 150
页数:10
相关论文
共 59 条
  • [1] A method of a lightning surge analysis recommended in Japan using EMTP
    Ametani, A
    Kawamura, T
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2005, 20 (02) : 867 - 875
  • [2] Behavior of MV Insulators Under Lightning-Induced Overvoltages: Experimental Results and Reproduction of Volt-Time Characteristics by Disruptive Effect Models
    Ancajima, Alejandro
    Carrus, Alys
    Cinieri, Enrico
    Mazzetti, Carlo
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2010, 25 (01) : 221 - 230
  • [3] Anderson J.G., 1982, TRANSMISSION LINE RE, V2nd, P545
  • [4] [Anonymous], 1985, IEEE T POWER AP SYST, V104, P919
  • [5] [Anonymous], 1997, IEEE Standard 1243-1997
  • [6] [Anonymous], 1991, GUID PROC EST LIGHT, P63
  • [7] [Anonymous], 2013, LIGHTN PAR ENG APPL
  • [8] [Anonymous], 1996, MODELS in ATP
  • [9] [Anonymous], 1940, ELECTRON ENG, V59, P598
  • [10] [Anonymous], 1986, EMTP Theory Book