A modified dielectric dissipation factor measurement technique for transformer insulating oil

被引:3
|
作者
Sur, Ujjal [1 ]
机构
[1] Future Inst Engn & Management, Dept Elect Engn, Kolkata, India
关键词
bridge network; dielectric loss; dissipation factor; transformer insulating oil; FREQUENCY-RESPONSE ANALYSIS; DIAGNOSIS;
D O I
10.1088/1361-6501/ac7634
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
This paper proposes a low cost mechanism to accurately measure the dissipation factor and its allied effect over transformer insulating oil. The measuring circuit is a modified De Sauty bridge network where the accurate parameter measurement can been performed. The effect of stray capacitance over dielectric loss and dissipation factor has been nullified by the application of operational amplifier in the circuit. Different samples of transformer insulating oil have been tested based on their aging and moisture content to check the reliability of the proposed measuring technique. Experimental result shows the efficacy of the proposed method when compared to existing IEC and ASTM standard procedures and commercial measuring devices. Measurement error analysis with repeatability and uncertainty calculation shows promising result and is within the acceptable limits.
引用
收藏
页数:9
相关论文
共 50 条
  • [1] Dielectric Strength Compatibility for Coconut Oil as a Transformer Insulating Oil
    Shill, Dayal Ch
    Das, Anu Kumar
    Chatterjee, Saibal
    PROCEEDINGS OF 2021 5TH INTERNATIONAL CONFERENCE ON CONDITION ASSESSMENT TECHNIQUES IN ELECTRICAL SYSTEMS (IEEE CATCON 2021), 2021, : 119 - 122
  • [2] The Influence of Dielectric Dissipation Factor on Transformer Frequency Response Analysis
    Bagheri, Mehdi
    Phung, B. T.
    Blackburn, Trevor
    2014 IEEE CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA (CEIDP), 2014, : 634 - 637
  • [3] Inhibition Technique of Transformer Insulating Oil Degradation - Evaluation of the Effectiveness of Oxidation Degradation Inhibitors
    Wada, Junichi
    Ueta, Genyo
    Okabe, Shigemitsu
    Amimoto, Tsuyoshi
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2013, 20 (05) : 1641 - 1648
  • [4] Investigating The Relationship Between Light Transmittance, Dissipation Factor (Tan α) and Transformer Oil Quality
    Sinclair, Noel
    Muir, Dave D.
    Chambers, Therese
    IEEE SOUTHEASTCON 2015, 2015,
  • [5] Dielectric Spectroscopy of Aqueous Insulating Oil Based on Maxwell-Wagner Modified Model
    Qian, Jiangbo
    Zhang, Zhilin
    Peng, Cheng
    Shao, Liwei
    Li, Gengda
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2024, 31 (05) : 2564 - 2571
  • [6] A Comparative Study of Dielectric Dissipation Factor Measurement under Very Low and Power Frequencies
    Morsalin, S.
    Phung, B. T.
    2017 3RD INTERNATIONAL CONFERENCE ON CONDITION ASSESSMENT TECHNIQUES IN ELECTRICAL SYSTEMS (CATCON), 2017, : 10 - 14
  • [7] Method to Evaluate the Degradation Condition of Transformer Insulating Oil - Establishment of the Evaluation Method and Application to Field Transformer Oil
    Wada, Junichi
    Ueta, Genyo
    Okabe, Shigemitsu
    Amimoto, Tsuyoshi
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2015, 22 (02) : 1266 - 1274
  • [8] Experiences with Detection of Transformer Failure Based on Insulating Oil Tests
    Rozga, Pawel
    Piotrowski, Tomasz
    Kozak, Ryszard
    2017 IEEE 19TH INTERNATIONAL CONFERENCE ON DIELECTRIC LIQUIDS (ICDL), 2017,
  • [9] Modeling of Dielectric Dissipation Factor Measurement for XLPE Cable Based on Davidson-Cole Model
    Morsalin, S.
    Phung, B. T.
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2019, 26 (03) : 1018 - 1026
  • [10] Effects of palm-based trimethylolpropane ester/mineral oil blending on dielectric properties and oxidative stability of transformer insulating liquid
    Raof, Nurliyana A.
    Yunus, Robiah
    Rashid, Umer
    Azis, Norhafiz
    Yaakub, Zaini
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2019, 26 (06) : 1771 - 1778