A novel intelligent fault diagnosis method for electrical equipment using infrared thermography

被引:76
作者
Zou, Hui [1 ]
Huang, Fuzhen [1 ]
机构
[1] Shanghai Univ Elect Power, Coll Automat Engn, Shanghai 200090, Peoples R China
关键词
Infrared thermography; Intelligent fault diagnosis; Feature extraction; Support vector machine; Parameter optimization; OPTIMIZATION;
D O I
10.1016/j.infrared.2015.08.019
中图分类号
TH7 [仪器、仪表];
学科分类号
0804 ; 080401 ; 081102 ;
摘要
Infrared thermography (IRT) has taken a very important role in monitoring and inspecting thermal defects of electrical equipment without shutting down, which has important significance for the stability of power systems. It has many advantages such as non-contact detection, freedom from electromagnetic interference, safety, reliability and providing large inspection coverage. Manual analysis of infrared images for detecting defects and classifying the status of equipment may take a lot of time and efforts, and may also lead to incorrect diagnosis results. To avoid the lack of manual analysis of infrared images, many intelligent fault diagnosis methods for electrical equipment are proposed, but there are two difficulties when using these methods: one is to find the region of interest, another is to extract features which can represent the condition of electrical equipment, as it is difficult to segment infrared images due to their over-centralized distributions and low intensity contrasts, which are quite different from those in visual light images. In this paper, a new intelligent diagnosis method for classification different conditions of electrical equipment using data obtained from infrared images is presented. In the first stage of our method, an infrared image of electrical equipment is clustered using K-means algorithm, then statistical characteristics containing temperature and area information are extracted in each region. In the second stage, in order to select the salient features which can better represent the condition of electrical equipment, some or all statistical characteristics from each region are combined as input data for support vector machine (SVM) classifier. To improve the classification performance of SVM, a coarse-to-fine parameter optimization approach is adopted. The performance of SVM is compared with that of back propagation neural network. The comparison results show that our method can achieve a better performance with accuracy 97.8495%. (C) 2015 Elsevier B.V. All rights reserved.
引用
收藏
页码:29 / 35
页数:7
相关论文
共 22 条
[1]   Recursive construction of output-context fuzzy systems for the condition monitoring of electrical hotspots based on infrared thermography [J].
Ahmed, Md. Manjur ;
Huda, A. S. N. ;
Isa, Nor Ashidi Mat .
ENGINEERING APPLICATIONS OF ARTIFICIAL INTELLIGENCE, 2015, 39 :120-131
[2]   Intelligent Thermographic Diagnostic Applied to Surge Arresters: A New Approach [J].
Almeida, Carlos A. Laurentys ;
Braga, Antonio P. ;
Nascimento, Sinval ;
Paiva, Vinicius ;
Martins, Helvio J. A. ;
Torres, Rodolfo ;
Caminhas, Walmir M. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2009, 24 (02) :751-757
[3]  
[Anonymous], 2010, ICMEE 2010 2010 2 IN
[4]  
[Anonymous], 2008, 6642008 DLT
[5]   Infrared thermography for condition monitoring - A review [J].
Bagavathiappan, S. ;
Lahiri, B. B. ;
Saravanan, T. ;
Philip, John ;
Jayakumar, T. .
INFRARED PHYSICS & TECHNOLOGY, 2013, 60 :35-55
[6]  
Cao Y., 2009, CHINA INT C ELECT DI, P1, DOI DOI 10.1109/CICED.2008.5211654
[7]   A distributed PSO-SVM hybrid system with feature selection and parameter optimization [J].
Huang, Cheng-Lung ;
Dun, Jian-Fan .
APPLIED SOFT COMPUTING, 2008, 8 (04) :1381-1391
[8]   Universal approximation using incremental constructive feedforward networks with random hidden nodes [J].
Huang, Guang-Bin ;
Chen, Lei ;
Siew, Chee-Kheong .
IEEE TRANSACTIONS ON NEURAL NETWORKS, 2006, 17 (04) :879-892
[9]   A new thermographic NDT for condition monitoring of electrical components using ANN with confidence level analysis [J].
Huda, A. S. N. ;
Taib, S. ;
Ghazali, K. H. ;
Jadin, M. S. .
ISA TRANSACTIONS, 2014, 53 (03) :717-724
[10]   Suitable features selection for monitoring thermal condition of electrical equipment using infrared thermography [J].
Huda, A. S. N. ;
Taib, S. .
INFRARED PHYSICS & TECHNOLOGY, 2013, 61 :184-191