Online monitoring of transformer through stream clustering of partial discharge signals

被引:7
作者
Firuzi, Keyvan [1 ,2 ]
Vakilian, Mehdi [1 ,2 ]
Phung, B. Toan [3 ]
Blackburn, Trevor [3 ]
机构
[1] Sharif Univ Technol, Elect Engn Dept, Tehran, Iran
[2] Sharif Univ Technol, Ctr Excellence Power Syst Management & Control, Tehran, Iran
[3] Univ New South Wales, Sch Elect Engn & Telecommun, Sydney, NSW, Australia
关键词
partial discharges; corona; power transformer insulation; condition monitoring; medium-voltage power system equipment; power transformer; high-voltage power system equipment; online real-time monitoring; partial discharge; DenStream method; Density Grids method; multisource discharge signal; internal discharge; surface discharge; corona discharge source; stream clustering algorithms; active sources; multiple defects; phase-resolved discharge patterns; PATTERN-RECOGNITION; SEPARATION;
D O I
10.1049/iet-smt.2018.5389
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The general method for identifying the partial discharge type in a power transformer is based on their fingerprints in the form of phase-resolved discharge patterns. In the case of multiple defects, traditional clustering methods can be applied for separation of active sources. However, such an approach is impractical for online real-time monitoring due to the very large data size. In this paper a new method using stream clustering is introduced. The method separates the active sources by processing the signal once it is captured, then only a synopsis of the discharge data is stored. Two stream clustering algorithms: Density Grids and DenStream are employed. Through measurements obtained from laboratory experimental setups (corona, surface discharge, transformer defect model) performance of the proposed algorithms are evaluated. It is shown that stream clustering method is able to separate the constituent components involved in the stream of a multi-source discharge signal without the need to store a large amount of information. The performance of the Density Grids method depends on a limited number of features that it can accommodate. In comparison, the DenStream method can capture more features which enable better separation of active sources at the expense of longer processing time.
引用
收藏
页码:409 / 415
页数:7
相关论文
共 28 条
[1]  
Aggarwal CC, 2007, KDD-2007 PROCEEDINGS OF THE THIRTEENTH ACM SIGKDD INTERNATIONAL CONFERENCE ON KNOWLEDGE DISCOVERY AND DATA MINING, P36
[2]   A method for discriminating original pulses in online partial discharge measurement [J].
Allahbakhshi, Mehdi ;
Akbari, Asghar .
MEASUREMENT, 2011, 44 (01) :148-158
[3]  
Andrade HCM, 2014, FUNDAMENTALS OF STREAM PROCESSING: APPLICATION DESIGN, SYSTEMS, AND ANALYTICS, P1, DOI 10.1017/CBO9781139058940
[4]   Partial Discharge and Noise Separation by Means of Spectral-power Clustering Techniques [J].
Ardila-Rey, J. A. ;
Martinez-Tarifa, J. M. ;
Robles, G. ;
Rojas-Moreno, M. V. .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2013, 20 (04) :1436-1443
[5]   Principal component and hierarchical cluster analyses as applied to transformer partial discharge data with particular reference to transformer condition monitoring [J].
Babnik, Tadeja ;
Aggarwal, Raj K. ;
Moore, Philip J. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2008, 23 (04) :2008-2016
[6]   Density-Based Clustering over an Evolving Data Stream with Noise [J].
Cao, Feng ;
Ester, Martin ;
Qian, Weining ;
Zhou, Aoying .
PROCEEDINGS OF THE SIXTH SIAM INTERNATIONAL CONFERENCE ON DATA MINING, 2006, :328-+
[7]   Advanced PD inference in on-field measurements. Part 2: Identification of defects in solid insulation systems [J].
Cavallini, A ;
Conti, M ;
Contin, A ;
Montanari, GC .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2003, 10 (03) :528-538
[8]   Time-frequency Sparsity Map on Automatic Partial Discharge Sources Separation for Power Transformer Condition Assessment [J].
Chan, Jeffery C. ;
Ma, Hui ;
Saha, Tapan K. .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2015, 22 (04) :2271-2283
[9]   An Efficient Diagnosis Method for Data Mining on Single PD Pulses of Transformer Insulation Defect Models [J].
Darabad, V. P. ;
Vakilian, M. ;
Phung, B. T. ;
Blackburn, T. R. .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2013, 20 (06) :2061-2072
[10]  
Firuzi K., PARTIAL DISCHARGES P