Research on Line Overload Emergency Control Strategy Based on the Source-Load Synergy Coefficient

被引:0
作者
Ma, Jing [1 ]
Kang, Wenbo [1 ]
Thorp, James S. [2 ]
机构
[1] North China Elect Power Univ, State Key Lab Alternate Elect Power Syst Renewabl, Beijing, Peoples R China
[2] Virginia Polytech Inst & State Univ, Bradley Dept Elect & Comp Engn, Blacksburg, VA 24061 USA
基金
国家重点研发计划;
关键词
Emergency control; Source-load synergy coefficient; Generator tripping and load shedding; Line overload; MODEL;
D O I
10.5370/JEET.2018.13.3.1079
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
A line overload emergency control strategy based on the source-load synergy coefficient is proposed in this paper. First, the definition of the source-load synergy coefficient is introduced. When line overload is detected, the source-load branch synergy coefficient and source-load distribution synergy coefficient are calculated according to the real-time operation mode of the system. Second, the generator tripping and load shedding control node set is determined according to the source-load branch synergy coefficient. And then, according to the line overload condition, the control quantity of each control node is determined using the Double Fitness Particle Swarm Optimization (DFPSO), with minimum system economic loss as the objective function. Thus load shedding for the overloaded line could be realized. On this basis, in order to guarantee continuous and reliable power supply, on the condition that no new line overload is caused, some of the untripped generators are selected according to the source-load distribution synergy coefficient to increase power output. Thus power supply could be restored to some of the shedded loads, and the economic loss caused by emergency control could be minimized. Simulation tests on the IEEE 10-machine 39-bus system verify the effectiveness and feasibility of the proposed strategy.
引用
收藏
页码:1079 / 1088
页数:10
相关论文
共 17 条
[1]   A new efficient nonlinear programming-based method for branch overload elimination [J].
Abrantes, HD ;
Castro, CA .
ELECTRIC POWER COMPONENTS AND SYSTEMS, 2002, 30 (06) :525-537
[2]   Analysis of overload conditions in distance relay under severe system contingencies [J].
Abu Bakar, Ab Halim ;
Yatim, Fazilah Mat ;
Yusof, Sallehuddin ;
Othman, Mohd Ridzal .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2010, 32 (05) :345-350
[3]  
Dai Y., 2006, ELECTR POW SYST RES, V64, P59
[4]   Application of active power sensitivity to frequency and voltage variations on load shedding [J].
Girgis, Adly A. ;
Mathure, Shruti .
ELECTRIC POWER SYSTEMS RESEARCH, 2010, 80 (03) :306-310
[5]  
Kennedy J, 1995, 1995 IEEE INTERNATIONAL CONFERENCE ON NEURAL NETWORKS PROCEEDINGS, VOLS 1-6, P1942, DOI 10.1109/icnn.1995.488968
[6]  
Liu K, 2011, AUTOMATION ELECT POW, V28, P32
[7]   A Fault Steady State Component-Based Wide Area Backup Protection Algorithm [J].
Ma, Jing ;
Li, Jinlong ;
Thorp, James S. ;
Arana, Andrew J. ;
Yang, Qixun ;
Phadke, A. G. .
IEEE TRANSACTIONS ON SMART GRID, 2011, 2 (03) :468-475
[8]   Criticality in a cascading failure blackout model [J].
Nedic, Dusko P. ;
Dobson, Ian ;
Kirschen, Daniel S. ;
Carreras, Benjamin A. ;
Lynch, Vickie E. .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2006, 28 (09) :627-633
[9]   Development of transient stability control system (TSC system) based on on-line stability calculation - Discussion [J].
Miller, NW ;
Larsen, E ;
Ihara, S .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1996, 11 (03) :1471-1471
[10]   Model predictive control to alleviate thermal overloads [J].
Otomega, Bogdan ;
Marinakis, Adamantios ;
Glavic, Mevludin ;
Van Cutsem, Thierry .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2007, 22 (03) :1384-1385