Optimal Sizing of UPQC Considering VA Loading and Maximum Utilization of Power-Electronic Converters

被引:52
作者
Ambati, Bharath Babu [1 ]
Khadkikar, Vinod [1 ]
机构
[1] Masdar Inst Sci & Technol, Inst Ctr Energy, Abu Dhabi, U Arab Emirates
关键词
Active power filters (APF); minimum VA loading; optimum rating; reactive power sharing; unified power-quality conditioner (UPQC); voltage sag; voltage swell;
D O I
10.1109/TPWRD.2013.2295857
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper introduces an optimum method to design a unified power-quality conditioner (UPQC) system with the minimum possible VA rating based on the compensation requirements. A set of generalized VA loading equations for the UPQC is derived, which are valid for all of the UPQC control approaches (such as UPQC-P, UPQC-Q, and UPQC - VA(min)). The variation in series and shunt inverters VA loadings of UPQC for the given compensation requirements is analyzed for all existing control approaches. A novel design method and the corresponding algorithm are proposed to size the major components in an UPQC, such as the series inverter, shunt inverter, and series transformer corresponding to the minimum possible overall VA rating. The VA rating and the utilization of power-electronic converters using the proposed design method are compared with those of UPQC-P, and UPQC - VA(min) approaches to show the effectiveness of the proposed design method.
引用
收藏
页码:1490 / 1498
页数:9
相关论文
共 12 条
  • [11] A review of active filters for power quality improvement
    Singh, B
    Al-Haddad, K
    Chandra, A
    [J]. IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 1999, 46 (05) : 960 - 971
  • [12] Yun MS, 2004, IEEE IND ELEC, P51