Application of infrared thermography for predictive/preventive maintenance of thermal defect in electrical equipment

被引:150
作者
Huda, A. S. Nazmul [1 ]
Taib, Soib [1 ]
机构
[1] Univ Sains Malaysia, Sch Elect & Elect Engn, Nibong Tebal 14300, Pulau Pinang, Malaysia
关键词
Infrared thermography; Electrical equipment; Preventive/predictive maintenance; Intelligent system; Discriminant analysis;
D O I
10.1016/j.applthermaleng.2013.07.028
中图分类号
O414.1 [热力学];
学科分类号
摘要
Internal heat of electrical equipment rises due to various reasons such as contact problems, unbalance loading, cracks in insulation, defective relays or terminal blocks, etc until eventual failure which can cause unplanned outages and possible injuries. Therefore, early prevention of thermal abnormalities in electrical equipment is necessary to avoid failure. Nowadays a fast, reliable, non-contact and cost effective infrared thermographic inspection system is being utilized widely for detecting where and how internal and external defects occur in equipment. The system collects data for investigating thermal condition through the analysis of thermal image of equipment. The image is captured by infrared camera without interrupting the running operation of system. Both preventive and predictive maintenance programs are adopted for defect diagnosis. Actually, the frequency and sequence of thermographic inspection depend on various factors including thermal condition, expense of a failure, type of production and age of equipment, etc. The objectives of this article are to discuss about preventive and predictive maintenance, thermal defects in electrical equipment and also an intelligent thermal defect identification system for accelerating the predictive defect diagnosis technique. The intelligent system proposes the application of artificial neural network and statistical features to detect the existence of defect within equipment by monitoring its thermal condition. Using discriminant analysis, the optimum features were chosen as the inputs of the neural network. The performances of the neural network were compared with the performances of discriminant analysis classifier. The comparison results showed that discriminant analysis classifier produced better performance with accuracy 82.40%. (C) 2013 Elsevier Ltd. All rights reserved.
引用
收藏
页码:220 / 227
页数:8
相关论文
共 28 条
  • [1] Thermographic study of energetic installations
    Al-Kassir, AR
    Fernandez, J
    Tinaut, FV
    Castro, F
    [J]. APPLIED THERMAL ENGINEERING, 2005, 25 (2-3) : 183 - 190
  • [2] Intelligent Thermographic Diagnostic Applied to Surge Arresters: A New Approach
    Almeida, Carlos A. Laurentys
    Braga, Antonio P.
    Nascimento, Sinval
    Paiva, Vinicius
    Martins, Helvio J. A.
    Torres, Rodolfo
    Caminhas, Walmir M.
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2009, 24 (02) : 751 - 757
  • [3] [Anonymous], 2006, FINDING REGIONS INTE
  • [4] [Anonymous], 2010, ICMEE 2010 2010 2 IN
  • [5] [Anonymous], 2011, STAND INFR INSP EL S
  • [6] [Anonymous], 2006, 70B NFPA
  • [7] ASTM, 2005, E1934 ASTM INT
  • [8] Infrared thermography for building diagnostics
    Balaras, CA
    Argiriou, AA
    [J]. ENERGY AND BUILDINGS, 2002, 34 (02) : 171 - 183
  • [9] Measurement of the temperature distribution on a circular plane fin by infrared thermography technique
    Bougriou, C
    Bessaïh, R
    Le Gall, R
    Solecki, JC
    [J]. APPLIED THERMAL ENGINEERING, 2004, 24 (5-6) : 813 - 825
  • [10] Automatic Diagnosis System of Electrical Equipment using Infrared Thermography
    Chou, Ying-Chieh
    Yao, Leehter
    [J]. 2009 INTERNATIONAL CONFERENCE OF SOFT COMPUTING AND PATTERN RECOGNITION, 2009, : 155 - 160