A practical design method for two-phase thermosyphon loop based on approaching degree to "ideal cycle"

被引:4
作者
Yang, Xiaorui [1 ]
Zhang, Penglei [1 ]
Li, Yue [1 ]
Zhang, Dalin [1 ]
机构
[1] Nanjing Univ Aeronaut & Astronaut, Coll Aerosp Engn, Inst Air Conditioning & Refrigerat, Nanjing 210016, Peoples R China
基金
中国国家自然科学基金;
关键词
Two-phase thermosyphon loop; Design method; Simulation; Efficiency; SEPARATE HEAT-PIPE; DATA CENTERS; MECHANICAL REFRIGERATION; THERMAL-CHARACTERISTICS; INTEGRATED-SYSTEM; PERFORMANCE; OPTIMIZATION; SIMULATION; STATIONS; RATIO;
D O I
10.1016/j.applthermaleng.2020.116059
中图分类号
O414.1 [热力学];
学科分类号
摘要
The two-phase thermosyphon loop (TPTL) has been widely used in data center cooling. But there is no practical design method and quantitative guidance to ensure a well-designed TPTL. In this paper, the approaching degree to "ideal cycle" epsilon is adopted as the efficiency indicator, based on which, a practical design method for TPTLs used in HVAC is proposed, ensuring the efficiency as well as the capacity of the designed TPTLs. In the design method, the area of the heat exchanger F is determined by the capacity Q, and the filling ratio FR, height difference Delta H, length L and diameter d of the connecting pipes are determined by the efficiency epsilon. The approaching degrees epsilon of TPTLs with filling ratios of 0.05-0.5, height differences of 0.2-5 m, connecting pipe lengths of 1-20 m, and connecting pipe diameters of 6.35-28.6 mm was simulated. For each TPTL, with capacity from 0 W to 10000 W, the recommended diameter, required minimum height difference, and optimal filling ratio were provided quantitatively, and practical design guidance was presented graphically. Additionally, a simple correction method for working fluids was proposed and validated, using five working fluids. Finally, a design example was provided to elaborate how to use the design method.
引用
收藏
页数:15
相关论文
共 37 条
[1]  
[Anonymous], 2019, STAND SPEC SEAML COP
[2]   Experimental investigations and modeling of a loop thermosyphon for cooling with zero electrical consumption [J].
Chehade, Ali ;
Louahlia-Gualous, Hasna ;
Le Masson, Stephane ;
Lepinasse, Eric .
APPLIED THERMAL ENGINEERING, 2015, 87 :559-573
[3]   Experiment research on influence factors of the separated heat pipe system, especially the filling ratio and Freon types [J].
Ding, Tao ;
Cao, Han Wen ;
He, Zhi Guang ;
Li, Zhen .
APPLIED THERMAL ENGINEERING, 2017, 118 :357-364
[4]   Thermo-economic analysis of steady state waste heat recovery in data centers using absorption refrigeration [J].
Ebrahimi, Khosrow ;
Jones, Gerard F. ;
Fleischer, S. .
APPLIED ENERGY, 2015, 139 :384-397
[5]  
Hideaki I.M.U.R.A., 1988, T JAPAN SOC REFRIGER
[6]  
Imura H., 1988, T JAPAN SOC REFRIG A, V5, P63
[7]  
Imura H., 2011, Trans. Jpn. Soc. Refrigerating Air Conditioning Eng., V6, P173
[8]   A Review on efficient thermal management of air- and liquid-cooled data centers: From chip to the cooling system [J].
Khalaj, Ali Habibi ;
Halgamuge, Saman K. .
APPLIED ENERGY, 2017, 205 :1165-1188
[9]   Heat transfer in the evaporator of an advanced two-phase thermosyphon loop [J].
Khodabandeh, R .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2005, 28 (02) :190-202
[10]   Thermal performance of a closed advanced two-phase thermosyphon loop for cooling of radio base stations at different operating conditions [J].
Khodabandeh, R .
APPLIED THERMAL ENGINEERING, 2004, 24 (17-18) :2643-2655