Critical Radius of Axial Magnetic-Field Contacts in Vacuum Interrupters

被引:7
作者
Liu, Zhiyuan [1 ]
Wang, Zhongyi [1 ]
Zheng, Yuesheng [1 ]
Wang, Jimei [1 ]
机构
[1] Xi An Jiao Tong Univ, Dept Elect Engn, State Key Lab Elect Insulat & Power Equipment, Xian 710049, Peoples R China
基金
中国国家自然科学基金;
关键词
Axial magnetic field (AMF); vacuum circuit breakers (VCBs); vacuum interrupters; HIGH-VOLTAGE;
D O I
10.1109/TPWRD.2008.2002976
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Vacuum circuit breakers (VCBs) are widely used to protect medium-voltage (MV) power distribution circuits. Since SF6 gas is specified as a global warming gas, VCBs are stepping into a higher voltage sector to protect power transmission circuits. Axial magnetic field (AMF) contacts are widely used in vacuum interrupters. In this paper, we propose a concept of critical radius of AMF contacts. When coil width and coil height are fixed, the axial magnetic flux density increases first with increasing contact diameter. Then, it reaches a maximum value. Thereafter, the axial magnetic flux density decreases. The contact radius corresponding to the maximum axial magnetic flux density is critical radius. The concept of critical radius is validated by coil-type AMF contacts and slot-type AMF contacts in MV vacuum interrupters with finite-element analysis. Critical radius is only related to contact geometry parameters and the current has no influence on critical radius. Critical radius increases with increasing contact gap, coil width, coil height, and thickness of the contact plate. In high-voltage AMF vacuum interrupters, axial magnetic flux density per kiloampere increases with increasing contact diameter since the critical radius is typically high with a high contact gap and it is in the rising branch. In an MV AMF vacuum interrupter, inter-rupting capacity could increase with an increase of the contact diameter with a different rising rate before and after the critical radius. This is expected to be experimentally validated.
引用
收藏
页码:672 / 678
页数:7
相关论文
共 21 条
  • [1] Study on a new single coil-type axial magnetic field contact for high-voltage vacuum interrupters
    Cheng, Shaoying
    Xiu, Shixin
    Liu, Zhiyuan
    Wang, Jimei
    [J]. IEEE TRANSACTIONS ON PLASMA SCIENCE, 2007, 35 (02) : 425 - 433
  • [2] Characteristics of a vacuum switching contact based on bipolar axial magnetic field
    Fenski, B
    Heimbach, M
    Lindmayer, M
    Shang, WK
    [J]. IEEE TRANSACTIONS ON PLASMA SCIENCE, 1999, 27 (04) : 949 - 953
  • [3] Vacuum interrupters with axial field contacts - 3-d finite element simulation and switching experiments
    Fenski, B
    Lindmayer, M
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 1997, 4 (04) : 407 - 412
  • [4] Fink H, 2002, INT SYM DISCH ELECTR, V20, P25, DOI 10.1109/ISDEIV.2002.1027302
  • [5] LEI Y, 1992, MAGNETIC FIELD CALCU
  • [6] LIU Z, 2004, Patent No. 2004200862768
  • [7] Development of high-voltage vacuum circuit breakers in China
    Liu, Zhiyuan
    Wang, Jimei
    Xiu, Shixin
    Wang, Zhongyi
    Yuan, Shun
    Jin, Li
    Zhou, Heming
    Yang, Ren
    [J]. IEEE TRANSACTIONS ON PLASMA SCIENCE, 2007, 35 (04) : 856 - 865
  • [8] Matsui Y., 2006, Proceedings of the XXIInd International Symposium on Discharges and Electrical Insulation in Vacuum, P253
  • [9] Three-dimensional magnetic field analysis of electrodes for VCBs
    Nitta, K
    Watanabe, K
    Kagenaga, K
    Mori, T
    Kaneko, E
    Somei, H
    Takahashi, H
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 1997, 12 (04) : 1520 - 1525