Autonomous microgrid operation subsequent to an anti-islanding scheme

被引:20
作者
Chandak, Sheetal [1 ]
Bhowmik, Pritam [1 ]
Mishra, Manohar [2 ]
Rout, Pravat Kumar [2 ]
机构
[1] Siksha O Anusandhan Univ, Elect Engn Dept, Bhubaneswar 751030, India
[2] Siksha O Anusandhan Univ, Elect & Elect Engn Dept, Bhubaneswar 751030, India
关键词
Microgrids; Distributed power generation system; Islanding; Power sharing; DISTRIBUTED GENERATION; DISTRIBUTION NETWORK; AC MICROGRIDS; PROTECTION; TRANSFORM; SYSTEMS;
D O I
10.1016/j.scs.2018.03.009
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
A microgrid is a scaled-down power grid, comprising of distributed power generations (DPGs) and loads. It generally operates in conjunction with the utility grid, but can also isolate to operate in "islanded mode" and serve independently according to the physical and/or economic circumstances. However, while incorporating the DPGs with the main grid, anti-islanding becomes a vital operational requirement. Thus, a novel anti-islanding scheme based on harmonic distortion is proposed in this study. To realize the full benefit of high DPGs penetration, stable operation of an islanded microgrid becomes a vital concern after the detection of an islanding event. Hence, this paper also investigates the capability of DPG units to sustain the transition, along with the post-islanding stability. Furthermore, the study also investigates the problem of power sharing during post-islanding condition and incorporates an intelligent power sharing technique for power balance, satisfying both voltage and frequency constraints. The studies show that the proposed approach not only ensures quick islanding detection with a reduced non-detection zone but also the stability of the microgrid, even during islanding transients. The time domain simulation results are found through MATLAB/SIMULINK environment and the corresponding analysis are presented to justify the efficacy of the proposed technique.
引用
收藏
页码:430 / 448
页数:19
相关论文
共 36 条
[1]  
Abedini M, 2018, SUSTAINABLE CITIES S
[2]   Economic and ecological aspects for microgrids deployment in India [J].
Ahmad, Furkan ;
Alam, Mohammad Saad .
SUSTAINABLE CITIES AND SOCIETY, 2018, 37 :407-419
[3]  
Amini MH, 2017, 2017 IEEE SECOND INTERNATIONAL CONFERENCE ON DC MICROGRIDS (ICDCM), P270, DOI 10.1109/ICDCM.2017.8001055
[4]  
[Anonymous], 2012, P IR C SMART GRIDS T
[5]   Nondetection Zone Assessment of an Active Islanding Detection Method and its Experimental Evaluation [J].
Bahrani, Behrooz ;
Karimi, Houshang ;
Iravani, Reza .
IEEE TRANSACTIONS ON POWER DELIVERY, 2011, 26 (02) :517-525
[6]   Control for Grid-Connected and Intentional Islanding Operations of Distributed Power Generation [J].
Balaguer, Irvin J. ;
Lei, Qin ;
Yang, Shuitao ;
Supatti, Uthane ;
Peng, Fang Zheng .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2011, 58 (01) :147-157
[7]   Bidirectional front end converter for DG with disturbance insensitivity and islanding-detection capability [J].
Brenna, Morris ;
Lazaroiu, George C. ;
Superti-Furga, Gabrio ;
Tironi, Enrico .
IEEE TRANSACTIONS ON POWER DELIVERY, 2008, 23 (02) :907-914
[8]  
Chandak S, 2015, 2015 IEEE POWER, COMMUNICATION AND INFORMATION TECHNOLOGY CONFERENCE (PCITC-2015), P497, DOI 10.1109/PCITC.2015.7438216
[9]  
Choudhury S, 2017, SUSTAINABLE CITIES S
[10]  
De Brabandere K., 2006, VOLTAGE FREQUENCY DR