摘要
A wide-area protection system against long-term voltage collapse was designed, implemented, tested, modified, and commissioned. The system is based on the SCADA system in southern Sweden, which has been complemented with input signals and equipment to execute action orders from the protection system. Bus voltages from the transmission system, reactive power output from generators, and current limiter information from main generators were used as input signals to the wide-area protection system. Actions from the protection system are shunt reactor disconnection/capacitor connection, start of gas turbines, emergency power request from the HVDC connection to Germany, low priority load disconnection, and shedding of high priority load.
引用
收藏
页码:30 / 35
页数:6
相关论文
共 3 条
[1]  
*CIGRE, 1995, 101 CIGRE
[2]  
*IEEE POW SYST REL, 1996, K12 IEEE POW SYST RE
[3]  
INGELSSON B, 1996, SPECIAL PROTECTION S