Monitored lighting energy savings from dimmable lighting controls in The New York Times Headquarters Building

被引:46
作者
Fernandes, Luis L. [1 ]
Lee, Eleanor S. [1 ]
DiBartolomeo, Dennis L. [1 ]
McNeil, Andrew [1 ]
机构
[1] Univ Calif Berkeley, Lawrence Berkeley Natl Lab, Bldg Technol & Urban Syst Dept, Environm Energy Technol Div, Berkeley, CA 94720 USA
关键词
Building energy-efficiency; Daylighting; Lighting control systems; CONTROL-SYSTEMS; PERFORMANCE; OFFICES;
D O I
10.1016/j.enbuild.2013.10.009
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Digital addressable, dimmable lighting controls were introduced to the US market in the early 2000s with the promise of energy savings while allowing greater flexibility than their analog counterpart. The New York Times Company installed this emerging technology, after thorough pre-procurement testing, in their new building in New York, NY. Four years after full occupancy (2007), the owner agreed to participate in post-occupancy monitoring of the lighting system to verify actual performance. Annual lighting energy savings from daylighting, setpoint tuning and occupancy controls were determined for the daylit, open-plan office areas on three typical floors (6th, 11th, and 20th) of the 51-story tower. Energy savings were calculated from data recorded by the lighting control system, after calibration through independent energy consumption measurements. Savings from dimming controls (daylighting and setpoint tuning) were 12.6 kWh/m(2) yr for the daylit spaces on the three floors overall, or 20%, relative to ASHRAE 90.1-2007. Against the prescriptive code in effect at the time of the building's construction (ASHRAE 90.1-2001), savings were 21.0 kWh/m(2) yr or 28%. Annual lighting energy use with all lighting control strategies was 33.9 kWh/m(2) yr in the daylit, open plan zones on average for the three floors. A simple payback analysis was conducted. (C) 2013 Elsevier B.V. All rights reserved.
引用
收藏
页码:498 / 514
页数:17
相关论文
共 20 条
  • [1] American Society of Heating Refrigerating Air-Conditioning Engineers, 2001, 9012001 ASHRAE
  • [2] American Society of Heating Refrigerating and Air-Conditioning Engineers (ASHRAE), 2010, 9012010 ASHRAE
  • [3] [Anonymous], 2005, LBNL57602
  • [4] [Anonymous], 2013, YORK TIMES BUILDING
  • [5] ASHRAE, 2007, 9012007 ASHRAE
  • [6] Birt B., 2009, LUX EUR 11 EUR LIGHT, P731
  • [7] Consolidated Edison Company of New York Inc., PSC 10 EL STAT MARK
  • [8] Consolidated Edison Company of New York Inc., PSC 10 EL, P63
  • [9] Energy saving lighting control systems for open-plan offices: A field study
    Galasiu, Anca D.
    Newsham, Guy R.
    Suvagau, Cristian
    Sander, Daniel M.
    [J]. LEUKOS, 2007, 4 (01) : 7 - 29
  • [10] Field-Measured Performance Evaluation of a Digital Daylighting System
    Granderson, Jessica
    Gaddam, Vasanth
    DiBartolomeo, Dennis
    Li, Xiaolei
    Rubinstein, Francis
    Das, Sushanta
    [J]. LEUKOS, 2010, 7 (02) : 85 - 101