Smoke confinement utilizing the USME ventilation mode for subway station fire

被引:37
作者
Luo, Na [1 ]
Li, Angui [1 ]
Gao, Ran [1 ]
Tian, Zhenguo [1 ]
Hu, Zhipei [1 ]
机构
[1] Xian Univ Architecture & Technol, Sch Environm & Municipal Engn, Xian 710055, Shaanxi, Peoples R China
基金
美国国家科学基金会;
关键词
Subway station; Ventilation modes; USME; Layout of vents; Heat release rate; CFD SIMULATION; LIFE SAFETY; EVACUATION;
D O I
10.1016/j.ssci.2014.06.002
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
Experiment and numerical simulation were performed to research the possibility of adopting different ventilation modes for smoke confinement in a subway station fire accident. Bench scale experiments were conducted in a 1:50 scale model of a subway station. Fire Dynamics Simulator software (FDS) was utilized to carry out numerical simulations, which conducted in a full scale subway station. Experiment result agreed well with simulation result and the research showed that the different ventilation mode had different efficacy of smoke confinement released by the fire in basement 2. In addition, when the USME ventilation mode was adopted and there were smoke exhausted from basement 2 and air supplied into the basement 1, the efficacy of smoke confinement was the best. According to these cases conducted in this paper, the layouts of the ventilation vents had little influence on the efficacy of smoke confinement. Once the HRR was too big, the concentration would pass 50 PPM and the amount of exhausted smoke should be increased
引用
收藏
页码:202 / 210
页数:9
相关论文
共 50 条
[21]   Numerical and experimental study on optimal running mode of smoke extraction system in a subway station in Beijing [J].
Yang, Yingxia ;
Chen, Chao ;
Fan, Hongming ;
Qu, Lu ;
Ren, Mingliang .
BUILDING SIMULATION 2007, VOLS 1-3, PROCEEDINGS, 2007, :1254-1261
[22]   Prediction of the spread of smoke in a huge transit terminal subway station under six different fire scenarios [J].
Gao, Ran ;
Li, Angui ;
Hao, Xinpeng ;
Lei, Wenjun ;
Deng, Baoshun .
TUNNELLING AND UNDERGROUND SPACE TECHNOLOGY, 2012, 31 :128-138
[23]   Pedestrian evacuation at the subway station under fire [J].
杨晓霞 ;
董海荣 ;
姚秀明 ;
孙绪彬 .
Chinese Physics B, 2016, 25 (04) :490-498
[24]   Smoke spreading analyses in a subway fire scale model [J].
Giachetti, B. ;
Couton, D. ;
Plourde, F. .
TUNNELLING AND UNDERGROUND SPACE TECHNOLOGY, 2017, 70 :233-239
[25]   The effect of PSD on life safety in subway station fire [J].
Roh, Jae Seong ;
Ryou, Hong Sun ;
Yoon, Sung Wook .
JOURNAL OF MECHANICAL SCIENCE AND TECHNOLOGY, 2010, 24 (04) :937-942
[26]   Research on thermal-driven smoke control by using smoke curtains during a subway platform fire [J].
Liu, Yongqiang ;
Liu, Fang ;
Weng, Miaocheng ;
Obadi, Imad ;
Geng, Pengqiang .
INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2022, 172
[27]   The effect of PSD on life safety in subway station fire [J].
Jae Seong Roh ;
Hong Sun Ryou ;
Sung Wook Yoon .
Journal of Mechanical Science and Technology, 2010, 24 :937-942
[28]   Comparative analysis of evacuation simulation for a subway station fire [J].
Liu, Q. Q. ;
Han, X. ;
Shang, K. ;
Wu, G. H. .
ISISS '2007: PROCEEDINGS OF THE INNOVATION AND SUSTAINABILITY OF STRUCTURES, VOLS 1 AND 2, 2008, :1166-1174
[29]   Experimental and numerical study on the smoke movement and smoke control strategy in a hub station fire [J].
Liu, Fang ;
Liu, Yongqiang ;
Xiong, Kang ;
Weng, Miaocheng ;
Wang, Jun .
TUNNELLING AND UNDERGROUND SPACE TECHNOLOGY, 2020, 96
[30]   Analysis of air curtain applied in subway station to prevent smoke [J].
Xie, J ;
He, JP ;
Zhou, R ;
Peng, HP .
PROGRESS IN SAFETY SCIENCE AND TECHNOLOGY, VOL V, PTS A AND B, 2005, 5 :1143-1146