Mitigation of Subsynchronous Resonance in power grid integrated with PV Power Station

被引:0
|
作者
Mittapally, Sravan Kumar [1 ]
Pang, Chengzong [1 ]
Renduchintala, Uday Kishan [1 ]
机构
[1] Wichita State Univ, Dept Elect Engn & Comp Sci, Wichita, KS 67260 USA
关键词
Subsynchronous Resonance; Serie compensation voltage; PV farm; RENEWABLE ENERGY;
D O I
暂无
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
This paper presents the alleviation of subsynchronous resonance (SSR) in the power system with large scale PV power station, in synchronous generator which is connected to series compensated transmission line. The rapid growth in utility connected PV farms has opened new possibilities, and due to its flexibility and dispatchability PV farms can handle the grid support functions more effectively, whereas its ability to mitigate the SSR is rarely investigated. In this study potential of PV farm to mitigate SSR is explored by augmenting the GSC control loop with damping controller using a control signal which is closely related to the network resonant mode, utility scale PV power stations are promising solutions to combat the increasing demand and grid functions. The simulation studies are performed in MATLAB/Simulink software using IEEE Second Benchmark Model (SBM) for SSR studies. PV farms provide more cost-effective solution compared to the FACTS devices of similar capacity for the assigned objective.
引用
收藏
页码:507 / 511
页数:5
相关论文
共 50 条
  • [1] Simulation and mitigation of subsynchronous resonance in power systems
    Varela, Jorge
    Parada, Miguel
    2021 IEEE IFAC INTERNATIONAL CONFERENCE ON AUTOMATION/XXIV CONGRESS OF THE CHILEAN ASSOCIATION OF AUTOMATIC CONTROL (IEEE IFAC ICA - ACCA2021), 2021,
  • [2] Subsynchronous resonance and its mitigation for power system with unified power flow controller
    Zhu, Xinyao
    Jin, Meng
    Kong, Xiangping
    Zhao, Jingbo
    Liu, Jiankun
    Zhou, Qian
    JOURNAL OF MODERN POWER SYSTEMS AND CLEAN ENERGY, 2018, 6 (01) : 181 - 189
  • [3] Subsynchronous resonance and its mitigation for power system with unified power flow controller
    Xinyao ZHU
    Meng JIN
    Xiangping KONG
    Jingbo ZHAO
    Jiankun LIU
    Qian ZHOU
    Journal of Modern Power Systems and Clean Energy, 2018, 6 (01) : 181 - 189
  • [4] RESEARCH ON THE GRID-CONNECTED PV POWER STATION
    Li Jing
    Xu Honghua
    Zhao Haixiang
    Peng Yanchang
    2008 CHINA INTERNATIONAL CONFERENCE ON ELECTRICITY DISTRIBUTION, VOLS 1 AND 2, 2009, : 664 - 672
  • [5] SUBSYNCHRONOUS RESONANCE OF A POWER STATION WITH TWO IDENTICAL GENERATING UNITS.
    Jennings, G.D.
    Harley, R.G.
    Levy, D.C.
    1600, (133):
  • [6] Eigenvalue Analysis of Subsynchronous Oscillation in Grid-connected PV Power Stations
    Yang, Lin
    Yu, Zhao
    Xu, Tao
    He, Jingbo
    Wang, Chao
    Pang, Chengzong
    PROCEEDINGS OF 2017 CHINA INTERNATIONAL ELECTRICAL AND ENERGY CONFERENCE (CIEEC 2017), 2017, : 285 - 290
  • [7] SUBSYNCHRONOUS RESONANCE OF A POWER-STATION WITH 2 IDENTICAL GENERATING-UNITS
    JENNINGS, GD
    HARLEY, RG
    LEVY, DC
    IEE PROCEEDINGS-C GENERATION TRANSMISSION AND DISTRIBUTION, 1986, 133 (01) : 33 - 43
  • [8] Analysis and Mitigation of Subsynchronous Resonance in a Korean Power Network with the First TCSC Installation
    Minh-Quan Tran
    Minh-Chau Dinh
    Lee, Seok-Ju
    Lee, Jea-In
    Park, Minwon
    Lee, Chur Hee
    Yoon, JongSu
    ENERGIES, 2019, 12 (15)
  • [9] Damping subsynchronous resonance in power systems
    Gupta, SK
    Gupta, AK
    Kumar, N
    IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 2002, 149 (06) : 679 - 688
  • [10] Impact of partial shading and PV array power on the performance of grid connected PV station
    Dabou, Rachid
    Sahouane, Nordine
    Necaibia, Ammar
    Mostefaoui, Mohammed
    Bouchafaa, Farid
    Rouabhia, Abdelkrim
    Ziane, Abderrezzaq
    Bouraiou, Ahmed
    2017 18TH INTERNATIONAL CONFERENCE ON SCIENCES AND TECHNIQUES OF AUTOMATIC CONTROL AND COMPUTER ENGINEERING (STA), 2017, : 476 - 481