Fault Location Algorithm for Non-Homogeneous Transmission Lines Considering Line Asymmetry

被引:53
|
作者
Liu, Yu [1 ]
Wang, Binglin [1 ,2 ,3 ,4 ]
Zheng, Xiaodong [5 ,6 ]
Lu, Dayou [1 ]
Fu, Minfan [1 ]
Tai, Nengling [5 ,6 ]
机构
[1] ShanghaiTech Univ, Sch Informat Sci & Technol, Shanghai 201210, Peoples R China
[2] Chinese Acad Sci, Shanghai Adv Res Inst, Shanghai, Peoples R China
[3] Chinese Acad Sci, Shanghai Inst Microsyst & Informat Technol, Shanghai, Peoples R China
[4] Univ Chinese Acad Sci, Beijing, Peoples R China
[5] Shanghai Jiao Tong Univ SJTU, Dept Elect Engn, Shanghai 200240, Peoples R China
[6] Minist Educ, Key Lab Control Power Transmiss & Convers SJTU, Shanghai 200240, Peoples R China
基金
中国国家自然科学基金;
关键词
Power transmission lines; Transmission line measurements; Fault location; Voltage measurement; Transmission line matrix methods; Mathematical model; Current measurement; Fault Location; Non-homogeneous Transmission Lines; Generalized Compact Model; Line Asymmetry; Multi-terminal Lines; MACHINE;
D O I
10.1109/TPWRD.2020.2968191
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This article presents a novel phasor domain approach to determine the location of faults in non-homogeneous transmission lines. Best implementation requires synchronized voltage and current phasor measurements at all terminals of the transmission line. The overall non-homogeneous transmission line model with fault is established by systematically combining the generalized compact models of all homogeneous line sections. The location of the fault is introduced as an additional state of the overall model. The derivation procedure of the model is without further assumptions, resulting in full consideration of three phase line asymmetry as well as distributed parameters of non-homogeneous transmission lines. Afterwards, the location of the fault is identified using the state estimation algorithm. Extensive numerical experiments in a two-terminal and a multi-terminal non-homogeneous transmission line demonstrate that the method has higher accuracy than existing fault location methods, independent of fault types, locations and impedances.
引用
收藏
页码:2425 / 2437
页数:13
相关论文
共 50 条
  • [21] A method for fault location compensation considering operating states of transmission lines
    Liu, Yadong
    Sheng, Gehao
    Sun, Xuri
    Gao, Sen
    Jiang, Xiuchen
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2012, 36 (13): : 92 - 96+115
  • [22] Accurate fault location algorithm for series compensated transmission lines
    Sadeh, J
    Ranjbar, AM
    Hadjsaid, N
    Feuillet, R
    2000 IEEE POWER ENGINEERING SOCIETY WINTER MEETING - VOLS 1-4, CONFERENCE PROCEEDINGS, 2000, : 2527 - 2532
  • [23] Accurate fault location algorithm for series compensated transmission lines
    Sadeh, J
    Hadjsaid, N
    Ranjbar, AM
    Feuillet, R
    IEEE TRANSACTIONS ON POWER DELIVERY, 2000, 15 (03) : 1027 - 1033
  • [24] A new single ended fault location algorithm for combined transmission line considering fault clearing transients without using line parameters
    Niazy, Ismail
    Sadeh, Javad
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2013, 44 (01) : 816 - 823
  • [25] Time-Domain Fault Location Algorithm for Double-Circuit Transmission Lines Connected to Large Scale Wind Farms
    Saber, A.
    Zeineldin, H. H.
    El-Fouly, Tarek H. M.
    Al-Durra, Ahmed
    IEEE ACCESS, 2021, 9 : 11393 - 11404
  • [26] Optimal estimate of transmission line fault location considering measurement errors
    Liao, Yuan
    Kezunovic, Mladen
    IEEE TRANSACTIONS ON POWER DELIVERY, 2007, 22 (03) : 1335 - 1341
  • [27] Unsynchronized fault location on untransposed transmission lines with fully distributed parameter model considering line parameter uncertainties
    Lu, Dian
    Liu, Yu
    Lu, Dayou
    Wang, Binglin
    Zheng, Xiaodong
    ELECTRIC POWER SYSTEMS RESEARCH, 2022, 202
  • [28] Transmission Line Fault Location Based on Improved Algorithm of Electromagnetic Time Reversal
    Liu, Qing
    Yang, Jiayi
    Fu, Yao
    Huang, Yuhe
    IEEE ACCESS, 2022, 10 : 37839 - 37847
  • [29] A fault location algorithm for transmission line based on ditributed parameter
    Chen, Z
    Luo, CM
    Su, JX
    Wu, XR
    SEVENTH INTERNATIONAL CONFERENCE ON DEVELOPMENTS IN POWER SYSTEM PROTECTION, 2001, (479): : 411 - 413
  • [30] Fault Location in Overhead Transmission Lines Based on Magnetic Signatures and on the Extended Kalman Filter
    De Oliveira Neto, Jesus Anicio
    Sartori, Carlos Antonio Franca
    Manassero Junior, Giovanni
    IEEE ACCESS, 2021, 9 : 15259 - 15270