Simulation study on the operating characteristics of the heat pipe for combined evaporative cooling of computer room air-conditioning system

被引:22
作者
Han, Zongwei [1 ]
Zhang, Yanqing [1 ]
Meng, Xin [1 ]
Liu, Qiankun [1 ]
Li, Weiliang [1 ]
Han, Yu [2 ]
Zhang, Yanhong [2 ]
机构
[1] Northeastern Univ, Sch Met & Mat, Shenyang 110819, Peoples R China
[2] Xinjiang Solar Technol Dev Co, Urumqi 830011, Peoples R China
关键词
Simulation study; Evaporative cooling; Separate type heat pipe; Mathematical model; Energy saving; DATA CENTERS; PERFORMANCE; EXCHANGERS; FLOW;
D O I
10.1016/j.energy.2016.01.009
中图分类号
O414.1 [热力学];
学科分类号
摘要
In order to improve the energy efficiency of air conditioning systems in computer rooms, this paper proposed a new concept of integrating evaporative cooling air-conditioning system with heat pipes. Based on a computer room in Shenyang, China, a mathematical model was built to perform transient simulations of the new system. The annual dynamical performance of the new system was then compared with a typical conventional computer room air-conditioning system. The result showed that the new integrated air-conditioning system had better energy efficiency, i.e. 31.31% reduction in energy consumption and 29.49% increase in COP (coefficient of performance), due to the adoption of evaporative condenser and the separate type heat pipe technology. Further study also revealed that the incorporated heat pipes enabled a 36.88% of decrease in the operation duration of the vapor compressor, and a 53.86% of reduction for the activation times of the compressor, which could lead to a longer lifespan of the compressor. The new integrated evaporative cooling air-conditioning system was also tested in different climate regions. It showed that the energy saving of the new system was greatly affected by climate, and it had the best effect in cold and dry regions like Shenyang with up to 31.31% energy saving. In some warm and humid climate regions like Guangzhou, the energy saving could be achieved up to 13.66%. (C) 2016 Elsevier Ltd. All rights reserved.
引用
收藏
页码:15 / 25
页数:11
相关论文
共 29 条
[1]   The application of heat pipe heat exchangers to improve the air quality and reduce the energy consumption of the air conditioning system in a hospital ward-A full year model simulation [J].
Ahmadzadehtalatapeh, M. ;
Yau, Y. H. .
ENERGY AND BUILDINGS, 2011, 43 (09) :2344-2355
[2]  
Becker M., 1986, HEAT TRANSFER MODERN
[3]   Measurements and predictions of the air distribution systems in high compute density (Internet) data centers [J].
Cho, Jinkyun ;
Lim, Taesub ;
Kim, Byungseon Sean .
ENERGY AND BUILDINGS, 2009, 41 (10) :1107-1115
[4]  
Comlan Fannoulean-Louis, 2015, APPL THERM ENG, V82, P306
[5]  
Dittus F., 1980, P 5 INT HEAT TRANSFE, P2275
[6]   Modelling thermostatic expansion valves [J].
Eames, Ian W. ;
Milazzo, Adriano ;
Maidment, Graeme G. .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2014, 38 :189-197
[7]   Performance simulation of refrigerated display cabinets operating with refrigerants R22 and R404A [J].
Ge, Y. T. ;
Cropper, R. .
APPLIED ENERGY, 2008, 85 (08) :694-707
[8]   Development of an integrated air conditioner with thermosyphon and the application in mobile phone base station [J].
Han, Linjun ;
Shi, Wenxing ;
Wang, Baolong ;
Zhang, Penglei ;
Li, Xianting .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2013, 36 (01) :58-69
[9]  
Hiroshi Endo, 2013, SUSTAIN COMPUT INF, P1
[10]   Effects of accumulator heat exchangers on the performance of a refrigeration system [J].
Kang, Hoon ;
Choi, Kwangmin ;
Park, Chasik ;
Kim, Yongchan .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2007, 30 (02) :282-289