Response Mechanism of DFIG to Transient Voltage Disturbance Under Commutation Failure of LCC-HVDC System

被引:20
作者
Zheng, Zixuan [1 ]
Ren, Jie [1 ]
Xiao, Xianyong [1 ]
Huang, Chunjun [1 ]
Wang, Yang [1 ]
Xie, Qi [1 ]
机构
[1] Sichuan Univ, Coll Elect Engn, Chengdu 610065, Peoples R China
基金
中国国家自然科学基金;
关键词
Reactive power; Transient analysis; Doubly fed induction generators; HVDC transmission; Rotors; Wind farms; Stators; DFIG; FRT; LCC-HVDC; commutation failure; FED INDUCTION GENERATOR; WIND TURBINES; STRATEGY;
D O I
10.1109/TPWRD.2020.3005720
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Commutation failure is one of the common faults in the line commutated converter high voltage direct current (LCC-HVDC) transmission system, which will lead to a transient voltage disturbance with the characteristic of "decrease first and then increase" at the feed end. Such a transient voltage may cause severe dynamic responses on the wind generator adjacent to the converter station, resulting in the tripping of large-scale wind turbines and even cascading failure. By analyzing the principle of the transient voltage, this paper investigates the response mechanism of doubly-fed induction generator (DFIG), involving the variation of electrical parameters and fault ride through (FRT) ability. Further verifications through simulations and experiments prove that under the disturbance of commutation failure, DFIG may suffer greater transient shocks compared to a single sag or swell disturbance event. Finally, some suggestions are put forward to mitigate the transient voltage and improve the transient response of DFIG.
引用
收藏
页码:2972 / 2979
页数:8
相关论文
共 19 条
[1]  
[Anonymous], WATER ECON POLICY
[2]   Doubly Fed Induction Generator Wind Turbine Systems Subject to Recurring Symmetrical Grid Faults [J].
Chen, Wenjie ;
Blaabjerg, Frede ;
Zhu, Nan ;
Chen, Min ;
Xu, Dehong .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2016, 31 (02) :1143-1160
[3]   Ride-Through Enhancement of Line-Commutated HVDC Link for Large Offshore Wind Parks [J].
Jafar, Muhammad ;
Molinas, Marta .
IECON: 2009 35TH ANNUAL CONFERENCE OF IEEE INDUSTRIAL ELECTRONICS, VOLS 1-6, 2009, :724-+
[4]  
Kundur P., 1994, Power System Stability and Control, P463
[5]   Impact of Climate Change on Water Resources in Agriculture [J].
Liu, Jing .
WATER ECONOMICS AND POLICY, 2018, 4 (02)
[6]   Wind turbines based on doubly fed induction generator under asymmetrical voltage dips [J].
Lopez, Jesus ;
Gubia, Eugenio ;
Sanchis, Pablo ;
Roboam, Xavier ;
Marroyo, Luis .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 2008, 23 (01) :321-330
[7]   Dynamic behavior of the doubly fed induction generator during three-phase voltage dips [J].
Lopez, Jesus ;
Sanchis, Pablo ;
Roboam, Xavier ;
Marroyo, Luis .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 2007, 22 (03) :709-717
[8]   An Enhanced Strategy to Inhibit Commutation Failure in Line-Commutated Converters [J].
Mirsaeidi, Sohrab ;
Dong, Xinzhou .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2020, 67 (01) :340-349
[9]   Impacts of Symmetrical and Asymmetrical Voltage Sags on DFIG-Based Wind Turbines Considering Phase-Angle Jump, Voltage Recovery, and Sag Parameters [J].
Mohseni, Mansour ;
Islam, Syed M. ;
Masoum, Mohammad A. S. .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2011, 26 (05) :1587-1598
[10]   Wind Farms Fault Ride Through Using DFIG With New Protection Scheme [J].
Okedu, Kenneth E. ;
Muyeen, S. M. ;
Takahashi, Rion ;
Tamura, Junji .
IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, 2012, 3 (02) :242-254