On cold-aisle containment of a container datacenter

被引:45
作者
Wang, Cheng-Hao [1 ]
Tsui, Yeng-Yung [1 ]
Wang, Chi-Chuan [1 ]
机构
[1] Natl Chiao Tung Univ, Dept Mech Engn, Hsinchu, Taiwan
关键词
Datacenter; Thermal management; Rack cooling index; Cold-aisle containment; Supplied heat index; Coanda effect; DATA CENTERS;
D O I
10.1016/j.applthermaleng.2016.10.089
中图分类号
O414.1 [热力学];
学科分类号
摘要
In this study, influences of various blockage arrangements as well as cold-aisle containment on the overall efficiency of a container datacenter are reported. The test container datacenter contains ten racks and the cold air is supplied from drop ceiling. The experiments are performed with each rack equally delivering a power of 3 kW. Eight different layouts are examined. Appreciable hot air recirculation prevails especially at the entrance of cold aisle. Adding blockage plates to the computer room air handler (CRAH) at the entrance of computer racks only improve marginally the associated rack cooling index (RCI). Layout with enclosing the end of cold aisle while let open the entrance of cold aisle also performs poorly. Full containment of the cold aisle with high jet air flowrate from the supplied grilles gives the worst performance. Layout with enclosing at the entrance of cold aisle but let open the end of cold aisle shows a much superior temperature distribution and a rather high RCI of 99%. Higher supplied flow may induce jet airflow pattern, causing the Coanda effect to result in fluctuating behaviors of RCI and SHI alongside the cold aisle (zigzag phenomenon). A lower supplied air flowrate without Coanda effect for a full containment design give the best overall performance. (C) 2016 Elsevier Ltd. All rights reserved.
引用
收藏
页码:133 / 142
页数:10
相关论文
共 14 条
  • [1] Thermal Characteristics of Open and Contained Data Center Cold Aisle
    Arghode, Vaibhav K.
    Sundaralingam, Vikneshan
    Joshi, Yogendra
    Phelps, Wally
    [J]. JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 2013, 135 (06):
  • [2] ASHRAE, 2011, ASHRAE TC 9.9
  • [3] Technological drivers in data centers and telecom systems: Multiscale thermal, electrical, and energy management
    Garimella, Suresh V.
    Persoons, Tim
    Weibel, Justin
    Yeh, Lian-Tuu
    [J]. APPLIED ENERGY, 2013, 107 : 66 - 80
  • [4] Gondipalli S., 2008, P 11 IEEE ITHERM C 2
  • [5] Herrlin MK, 2005, ASHRAE TRAN, V111, P725
  • [6] Koomey Jonathan., 2011, A report by Analytical Press, completed at the request of The New York Times
  • [7] Worldwide electricity used in data centers
    Koomey, Jonathan G.
    [J]. ENVIRONMENTAL RESEARCH LETTERS, 2008, 3 (03)
  • [8] Experimental investigations of air conditioning solutions in high power density data centers using a scaled physical model
    Nada, S. A.
    Elfeky, K. E.
    Attia, Ali M. A.
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION, 2016, 63 : 87 - 99
  • [9] Saurabh K.S., 2012, P INT C THERM THERM
  • [10] Schmidt R., 2011, P PAC RIM TECHN C EX