Heat and mass transfer in liquid desiccant air-conditioning process at low flow conditions

被引:19
作者
Peng, S. W. [1 ]
Pan, Z. M. [2 ]
机构
[1] Thermal Res & Applicat Ltd, Edmonton, AB T6R 0H6, Canada
[2] Wuhan ES Power Technol Ltd, Wuhan 430074, Peoples R China
关键词
Liquid desiccant; Air-conditioning; HVAC; Non-equilibrium heat and mass transfer; DEHUMIDIFICATION; SYSTEM;
D O I
10.1016/j.cnsns.2009.01.009
中图分类号
O29 [应用数学];
学科分类号
070104 ;
摘要
This paper investigates the transient heat and mass transfer in liquid desiccant air-conditioning process at low flow conditions. Using local volumetric average approach, one-dimensional non-equilibrium heat and mass transfer models are developed to describe the humid air and liquid desiccant interaction at counter flow configuration. Using triethylene glycol solution as desiccant, some experimental studies are completed. Experimental results are used to justify the numerical models. Numerical results are then obtained to demonstrate process characteristics. The models include a transient desiccant flow model for initial liquid desiccant building-up process, empirical wetted specific surface ratio for mass transfer, and heat and mass transfer coefficients. The objective of this research is to develop a process analytical tool for liquid desiccant air-conditioner design. (C) 2009 Elsevier B.V. All rights reserved.
引用
收藏
页码:3599 / 3607
页数:9
相关论文