Experimental investigation on thermal and mechanical behaviour of composite floors exposed to standard fire

被引:49
作者
Li, Guo-Qiang [1 ,3 ]
Zhang, Nasi [2 ]
Jiang, Jian [3 ]
机构
[1] Tongji Univ, State Key Lab Disaster Reduct Civil Engn, Shanghai 200092, Peoples R China
[2] Genex Syst, Newport News, VA 23606 USA
[3] Tongji Univ, Coll Civil Engn, Shanghai 200092, Peoples R China
基金
中国国家自然科学基金;
关键词
Fire resistance; Experimental investigation; Composite floor; Unprotected secondary beam; Direction of rib; Location of reinforcement; EC4; DIFFERENT HEATING REGIMES; STRUCTURAL BEHAVIOR; MEMBRANE ACTION; CONCRETE SLABS; COMPARTMENT;
D O I
10.1016/j.firesaf.2017.02.009
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
This paper presents experimental investigations on the thermal and mechanical behavior of composite floors subjected to ISO standard fire. Four 5.2 mx3.7 m composite slabs are tested with different combinations of the presence of one unprotected secondary beam, direction of ribs, and location of the reinforcement. The experimental results show that the highest temperature in the reinforcements occurs during the cooling phase (30-50 degrees C increment after 10-min cooling). The temperature at the unexposed side of the slabs is below 100 degrees C up to 100-min heating, compared to the predicted fire resistance close to 90 mins from EC4. For the slabs without secondary beams, the cracks first occur around the boundaries of the slab, while for the slabs supported by one unprotected secondary beam, concrete cracks first occur on the top of the slab above the beam due to the negative bending moment, and later on develop around boundaries. Debonding is observed between the steel deck and concrete slab. The secondary beam significantly impacts the deformation shape of tested slabs. Although a large deflection, 1/20 of the span length, is reached in the tests, the composite slabs can still provide sufficient load-bearing capacity due to membrane action. The occurrence of tensile membrane action is confirmed by the measured tensile stress in the reinforcement and compressive stress in the concrete. A comparison between measured and predicted fire resistance of the slabs indicates that EC4 calculations might be used for the composite slabs beyond the specified geometry limit, and the prediction is conservative.
引用
收藏
页码:63 / 76
页数:14
相关论文
共 38 条
[21]   Thermal behaviour of a gypsum fibre board associated with rigid polyurethane foam under standard fire conditions [J].
Le Dreau, Jerome ;
Jensen, Rasmus Lund ;
Kolding, Klaus .
6TH INTERNATIONAL BUILDING PHYSICS CONFERENCE (IBPC 2015), 2015, 78 :2736-2741
[22]   A numerical investigation of 3D structural behaviour for steel-composite structures under various travelling fire scenarios [J].
Nan, Zhuojun ;
Dai, Xu ;
Chen, Haimin ;
Welch, Stephen ;
Usmani, Asif .
ENGINEERING STRUCTURES, 2022, 267
[23]   Experimental investigation of behavior of reinforced high-strength concrete walls under standard fire [J].
Chen, Jun ;
Ji, Yukun ;
Xu, Yunhu ;
Wang, Gaoxin ;
Hu, Kunzhen .
JOURNAL OF BUILDING ENGINEERING, 2024, 87
[24]   Experimental investigation on the fire behaviour of rectangular and elliptical slender concrete-filled tubular columns [J].
Espinos, A. ;
Romero, M. L. ;
Serra, E. ;
Hospitaler, A. .
THIN-WALLED STRUCTURES, 2015, 93 :137-148
[25]   Experimental study into the behaviour of profiled composite walls under combined axial and thermal loadings [J].
Le, Quang X. ;
Dao, Vinh T. N. ;
Torero, Jose L. ;
Ngo, Tuan D. .
ENGINEERING STRUCTURES, 2020, 210
[26]   Thermal behaviour of a steel door frame subjected to the standard fire of ISO 834: Measurements, numerical simulation and parameter study [J].
Ghazi Wakili, K. ;
Wullschleger, L. ;
Hugi, E. .
FIRE SAFETY JOURNAL, 2008, 43 (05) :325-331
[27]   Physical, Mechanical, thermal and fire behaviour of recycled aggregate concrete block wall system with rice husk insulation [J].
Ma, Wenzhuo ;
Kolb, Torsten ;
Ruether, Norbert ;
Meinlschmidt, Peter ;
Chen, Haoze ;
Yan, Libo .
ENERGY AND BUILDINGS, 2024, 320
[28]   Experimental and numerical investigation of short-term behaviour of CLT-steel composite beams [J].
Hassanieh, A. ;
Valipour, H. R. ;
Bradford, M. A. .
ENGINEERING STRUCTURES, 2017, 144 :43-57
[29]   Experimental, numerical and analytical investigation of fire resistance of prefabricated angle steel lattice concrete composite column [J].
Zhang, Yanhong ;
Lou, Guobiao ;
Zhang, Chenhao ;
Zheng, Xiaofeng .
ENGINEERING STRUCTURES, 2025, 341
[30]   Experimental Investigation on Fire Behavior and Quantitative Restraint Forces of Steel-Concrete Composite Floor Systems [J].
Zhang, Dashan ;
Lin, Xuhua ;
Wang, Huiqing ;
Dong, Yuli ;
Zhang, Jianchun ;
Hu, Haocan .
JOURNAL OF STRUCTURAL ENGINEERING, 2022, 148 (10)