On heat and moisture transfer characteristics of a desiccant dehumidification unit using fin tube heat exchanger with silica gel coating

被引:46
作者
Zhao, Y. [1 ]
Dai, Y. J. [1 ]
Ge, T. S. [1 ]
Sun, X. Y. [1 ]
Wang, R. Z. [1 ]
机构
[1] Shanghai Jiao Tong Univ, Inst Refrigerat & Cryogen, Shanghai Engn Res Ctr Solar Power & Refrigerat, MOE China, Shanghai 200240, Peoples R China
关键词
Desiccant dehumidification; Heat transfer; Moisture transfer; Silica gel coating; Fitted calculation; PERFORMANCE; SYSTEM; COILS;
D O I
10.1016/j.applthermaleng.2015.07.075
中图分类号
O414.1 [热力学];
学科分类号
摘要
In this paper, the heat and moisture transfer characteristics of a desiccant dehumidification unit using fin-tube heat exchanger with silica gel coating have been experimentally investigated. The present study focuses on the analysis of air side heat and moisture transfer performance in dehumidification mode. The empirical formula on Nusselt and Sherwood numbers were deducted and curve fitted from the test results under various operation conditions, using the non-linear least square method. The typical operation condition is that the air side Reynolds number ranges between 220 and 550 and tube side cooling water flow rate is about 7.7 L/min. Further tests indicate that the correlations of Nusselt and Sherwood number on air side of the unit agree well with the test results, and the mean errors are about +/- 10% and +/- 12%, respectively. Finally, the improvements of the operation and configuration parameters of this novel heat and moisture transfer components are discussed with those formulas. It is found that the correlated formulas provide the theoretical basis and practical experience for design and optimization of the desiccant dehumidification unit using fin tube heat exchanger with silica gel coating. (C) 2015 Elsevier Ltd. All rights reserved.
引用
收藏
页码:308 / 317
页数:10
相关论文
共 26 条
[1]   Dynamic performance assessment of a micro-trigeneration system with a desiccant-based air handling unit in Southern Italy climatic conditions [J].
Angrisani, Giovanni ;
Roselli, Carlo ;
Sasso, Maurizio ;
Tariello, Francesco .
ENERGY CONVERSION AND MANAGEMENT, 2014, 80 :188-201
[2]   New family of solid sorbents for adsorptive cooling: Material scientist approach [J].
Aristov Yu.I. .
Journal of Engineering Thermophysics, 2007, 16 (2) :63-72
[3]   Field performance measurements of a heat pump desiccant unit in dehumidification mode [J].
Aynur, T. N. ;
Hwang, Y. H. ;
Radermacher, R. .
ENERGY AND BUILDINGS, 2008, 40 (12) :2141-2147
[5]  
Dunkle R.C., 1965, Aust. Mech. Chem. Eng. Transm, V1, P73
[6]   Operational experiences with solar air collector driven desiccant cooling systems [J].
Eicker, Ursula ;
Schneider, Dietrich ;
Schumacher, Juergen ;
Ge, Tianshu ;
Dai, Yanjun .
APPLIED ENERGY, 2010, 87 (12) :3735-3747
[7]   Simulation-optimization of solar-assisted desiccant cooling system for subtropical Hong Kong [J].
Fong, K. F. ;
Chow, T. T. ;
Lin, Z. ;
Chan, L. S. .
APPLIED THERMAL ENGINEERING, 2010, 30 (2-3) :220-228
[8]   Performance study of silica gel coated fin-tube heat exchanger cooling system based on a developed mathematical model [J].
Ge, T. S. ;
Dai, Y. J. ;
Wang, R. Z. .
ENERGY CONVERSION AND MANAGEMENT, 2011, 52 (06) :2329-2338
[9]   Experimental comparison and analysis on silica gel and polymer coated fin-tube heat exchangers [J].
Ge, T. S. ;
Dai, Y. J. ;
Wang, R. Z. ;
Peng, Z. Z. .
ENERGY, 2010, 35 (07) :2893-2900
[10]   Use of compound desiccant to develop high performance desiccant cooling system [J].
Jia, C. X. ;
Dai, Y. J. ;
Wu, J. Y. ;
Wang, R. Z. .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2007, 30 (02) :345-353