Experimental analysis on performance of high temperature heat pump and desiccant wheel system

被引:62
作者
Sheng, Ying [1 ]
Zhang, Yufeng [1 ]
Deng, Na [1 ]
Fang, Lei [2 ]
Nie, Jinzhe [2 ]
Ma, Lijun [1 ]
机构
[1] Tianjin Univ, Sch Environm Sci & Engn, Tianjin 300072, Peoples R China
[2] Tech Univ Denmark, Int Ctr Indoor Environm & Energy, DK-2800 Lyngby, Denmark
关键词
Desiccant wheel; High temperature heat pump; Coefficient of performance; ENERGY EFFICIENCY; DEHUMIDIFICATION; HUMIDITY;
D O I
10.1016/j.enbuild.2013.07.058
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
In order to solve the problem of high energy consumption for regeneration of desiccant wheel in the rotary desiccant system, high temperature heat pump and desiccant wheel (HTHP&DW) system and corresponding air conditioning unit is built and tested in the extensive thermal hygrometric environment. When the mixture refrigerant BY-3 is involved in the air source heat pump, the supply air temperatures are in the range as expected except that when in the extreme hot environment (above 36 C), dehumidification capability are satisfied and the regeneration temperatures can satisfy the regeneration requirement of desiccant without additional heat. It is also found that outdoor air temperature, humidity ratio and regeneration air flow rate have great impact on the performance of heat pump based on the coefficient of performance (COP) evaluated. COP is not quite high, as the maximum value is 2.26 for heat pump and 2.08 for whole system respectively. Hence several suggestions are made for optimizing the system which is also helpful for facilitating the development of mature product. As a conclusion, HTHP&DW system could be a potential alternative with effective operation which can be promoted in most areas of China based on the result of our experiment. (C) 2013 Elsevier B.V. All rights reserved.
引用
收藏
页码:505 / 513
页数:9
相关论文
共 30 条
[1]   Experimental analysis on the dehumidification and thermal performance of a desiccant wheel [J].
Angrisani, Giovanni ;
Minichiello, Francesco ;
Roselli, Carlo ;
Sasso, Maurizio .
APPLIED ENERGY, 2012, 92 :563-572
[2]   Desiccant wheel regenerated by thermal energy from a microcogenerator: Experimental assessment of the performances [J].
Angrisani, Giovanni ;
Capozzoli, Alfonso ;
Minichiello, Francesco ;
Roselli, Carlo ;
Sasso, Maurizio .
APPLIED ENERGY, 2011, 88 (04) :1354-1365
[3]   Experimental investigation to optimise a desiccant HVAC system coupled to a small size cogenerator [J].
Angrisani, Giovanni ;
Minichiello, Francesco ;
Roselli, Carlo ;
Sasso, Maurizio .
APPLIED THERMAL ENGINEERING, 2011, 31 (04) :506-512
[4]   Desiccant HVAC system driven by a micro-CHP: Experimental analysis [J].
Angrisani, Giovanni ;
Minichiello, Francesco ;
Roselli, Carlo ;
Sasso, Maurizio .
ENERGY AND BUILDINGS, 2010, 42 (11) :2028-2035
[5]  
[Anonymous], STAND REF DAT 23 VER
[6]   Field performance measurements of a heat pump desiccant unit in dehumidification mode [J].
Aynur, T. N. ;
Hwang, Y. H. ;
Radermacher, R. .
ENERGY AND BUILDINGS, 2008, 40 (12) :2141-2147
[7]   Potential of solar heat pipe vacuum collectors in the desiccant cooling process: Modelling and experimental results [J].
Bourdoukan, P. ;
Wurtz, E. ;
Joubert, P. ;
Sperandio, M. .
SOLAR ENERGY, 2008, 82 (12) :1209-1219
[8]   Experimental study of an air-source heat pump for simultaneous heating and cooling - Part 1: Basic concepts and performance verification [J].
Byrne, Paul ;
Miriel, Jacques ;
Lenat, Yves .
APPLIED ENERGY, 2011, 88 (05) :1841-1847
[9]  
Cao D., 2003, REFRIGERANT MANUAL
[10]  
Chen C., 2011, T TIANJIN U, V17, P386