Real scale tests on cable tray fires to simulate actual end user's condition

被引:0
|
作者
Wang Xinqun [1 ]
Liao Guangxuan [1 ]
Xu Tianrui [1 ]
Cai Xin [1 ]
机构
[1] Univ Sci & Technol China, State Key Lab Fire Sci, Hefei 230027, Anhui, Peoples R China
来源
PROGRESS IN SAFETY SCIENCE AND TECHNOLOGY, VOL 6, PTS A AND B | 2006年 / 6卷
关键词
real scale; cable tray fire; horizontal and vertical orientation; flame spread rate; fireproof tray; fire penetration prevention;
D O I
暂无
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
Six real scale cable tray fire tests both in horizontal and vertical orientation to simulate actual end user's environments were carried out. The flame spread rates in different initial condition were investigated, and performance of both fireproof cable tray and fire penetration prevention material was examined also. Digital video camera was employed to record flame propagation and thermocouples were used for measurement of temperature. The results indicate that the peck temperature of cable tray fires in the tests is between 800 degrees C and 900 degrees C, cable tray fires in horizontal orientation is ventilation controlled combustion, and vertical orientation cable tray fires are much more severe than that of horizontal orientation. It's shown that the available fireproof cable tray can not protect cables inside under fire condition, while the performance of fire penetration prevention material is quite perfect.
引用
收藏
页码:765 / 769
页数:5
相关论文
共 12 条
  • [11] International PCOS guideline clinical research priorities roadmap: a co-designed approach aligned with end-user priorities in a neglected women's health condition
    Teede, H. J.
    Gibson, M.
    Laven, J.
    Dokras, A.
    Moran, L. J.
    Piltonin, T.
    Costello, M.
    Mousa, A.
    Joham, A. E.
    Tay, C. T.
    ECLINICALMEDICINE, 2024, 78
  • [12] Different versions of Glasgow coma scale in British hospitals - The 14 point scale may be worth defending - Distinction must be made between real clinical condition and numbers - Author's reply
    Wiese, M
    BRITISH MEDICAL JOURNAL, 2004, 328 (7431): : 110 - 110