Impulse Breakdown Characteristics of Transformer Oil with Cellulose Particles in Quasi-Uniform Field

被引:7
作者
Guo, Ruochen [1 ]
Wang, Zhen [1 ]
He, Cong [1 ]
Meng, Xuan [1 ]
Li, Junhao [1 ]
Han, Xutao [2 ]
机构
[1] Xi An Jiao Tong Univ, State Key Lab Elect Insulat & Power Equipment, Xian 710049, Peoples R China
[2] Xidian Univ, Sch Aerosp Sci & Technol, Xian 710126, Peoples R China
基金
中国国家自然科学基金;
关键词
Electrodes; Electric breakdown; Oils; Lightning; Oil insulation; Electric fields; Power transformer insulation; impulse breakdown characteristics; transformer oil; cellulose particle; standard lightning impulse (SLI); oscillating lightning impulse (OLI);
D O I
10.1109/TDEI.2020.009064
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This study presents an experimental comparison of the breakdown characteristics of oil samples with four cellulose particle content levels in a quasi-uniform electric field under lightning impulse voltage. For the experiment to resemble the actual working conditions of transformers and meet the on-site withstand impulse voltage test requirements, both the standard lightning voltage (SLI) and oscillating lightning impulse (OLI) are considered. The experimental results show that an increase in the number of cellulose particles directly weakens the oil insulation strength. At the same particle content level, the oil breakdown voltage under OLI is higher than that under SLI, and the breakdown time lag under OLI is longer than that under SLI. The breakdown time lag is more sensitive to the effect of particle content under SLI. This work is beneficial in deepening the understanding of the impulse breakdown characteristics of transformer oil within cellulose particles and in providing references for the on-site impulse test of oil-immersed power transformers.
引用
收藏
页码:107 / 115
页数:9
相关论文
共 24 条
  • [1] [Anonymous], 2005, 600603 IEC
  • [2] Accumulation Behaviors of Different Particles and Effects on the Breakdown Properties of Mineral Oil under DC Voltage
    Dan, Min
    Hao, Jian
    Liao, Ruijin
    Cheng, Lin
    Zhang, Jie
    Li, Fei
    [J]. ENERGIES, 2019, 12 (12)
  • [3] Guo R., IEEE T DIELECTR ELEC
  • [4] Guo RC, 2020, IEEE T DIELECT EL IN, V27, P812, DOI [10.1109/TDEI.2020.008636, 10.1109/tdei.2020.008642]
  • [5] Effect of Moisture on Particles Accumulation and Oil Breakdown Characteristics in Mineral Oil and Natural Ester Under Non-Uniform DC Electrical Field
    Hao, Jian
    Dan, Min
    Liao, Ruijin
    Li, Jian
    [J]. IEEE ACCESS, 2019, 7 : 101785 - 101794
  • [6] Comparative study on the dynamic migration of cellulose particles and its effect on the conductivity in natural ester and mineral oil under DC electrical field
    Hao, Jian
    Liao, Ruijin
    Dan, Min
    Li, Yanqing
    Li, Jian
    Liao, Qiang
    [J]. IET GENERATION TRANSMISSION & DISTRIBUTION, 2017, 11 (09) : 2375 - 2383
  • [7] Influence of carbon particles on the breakdown voltage of transformer oil
    Krins, M
    Borsi, H
    Gockenbach, E
    [J]. ICDL 1996 - 12TH INTERNATIONAL CONFERENCE ON CONDUCTION AND BREAKDOWN IN DIELECTRIC LIQUIDS, 1996, : 296 - 299
  • [8] Breakdown Characteristics of Transformer Oil in a Uniform Field under Oscillating Impulse Voltage
    Li, Junhao
    Zhang, Liang
    Jin, Yuhui
    Yao, Xiu
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2017, 24 (02) : 984 - 990
  • [9] Partial Discharge Characteristics over Differently Aged Oil/pressboard Interfaces
    Li, Junhao
    Si, Wenrong
    Yao, Xiu
    Li, Yanming
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2009, 16 (06) : 1640 - 1647
  • [10] Breakdown and Withstand Strengths of Ester Transformer Liquids in a Quasi-uniform Field under Impulse Voltages
    Liu, Q.
    Wang, Z. D.
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2013, 20 (02) : 571 - 579