Saturation Nucleate Boiling and Correlations for PF-5060 Dielectric Liquid on Inclined Rough Copper Surfaces

被引:27
作者
El-Genk, Mohamed S. [1 ,2 ]
Suszko, Arthur [3 ]
机构
[1] Univ New Mexico, Inst Space & Nucl Power Studies, Dept Chem & Nucl Engn, Albuquerque, NM 87131 USA
[2] Univ New Mexico, Dept Mech Engn, Albuquerque, NM 87131 USA
[3] Univ New Mexico, Dept Mech Engn, Inst Space & Nucl Power Studies, Albuquerque, NM 87131 USA
来源
JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME | 2014年 / 136卷 / 08期
关键词
saturation boiling; dielectric liquids; electronics cooling; nucleate boiling correlations; surface inclination; rough copper surfaces; immersion cooling; HEAT-TRANSFER; POROUS GRAPHITE; HFE-7100;
D O I
10.1115/1.4027365
中图分类号
O414.1 [热力学];
学科分类号
摘要
Saturation pool boiling experiments of degassed PF-5060 dielectric liquid investigated nucleate boiling on 13 Cu surfaces with average roughness, Ra, of 0.039 (smooth polished) to 1.79 mu m at six inclination angles, theta, from 0 deg (upward facing) to 180 deg (downward facing). Values of the nucleate boiling heat transfer coefficient, h(NB), in the upward facing orientation increase with increasing surface roughness and are correlated in terms of the applied heat flux, q: h(NB) = A q(B). The exponent "B" decreases from 0.81 to 0.69 as Ra increases from 0.039 to 1.79 mu m, while the coefficient "A" increases with Ra to the power 0.24. The values of the maximum heat transfer coefficient, h(MNB), which occurs near the end of the fully developed nucleate boiling region, increase with increasing Ra and decreasing inclination angle. In the upward facing orientation, h(NB) increases by similar to 58% with increasing Ra from 0.134 to 1.79 mu m, while h(MNB) increases by more than 150% compared with that on smooth-polished Cu. Values of h(MNB) in the downward facing orientation are similar to 40% of those in the upward facing orientation.
引用
收藏
页数:10
相关论文
共 34 条
[1]  
3M, 2013, PERF FLUID PF 5060 P
[2]   Microelectronic Cooling by Enhanced Pool Boiling of a Dielectric Fluorocarbon Liquid [J].
Anderson, T. M. ;
Mudawar, I. .
JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 1989, 111 (1-4) :752-759
[3]   Heater orientation effects on pool boiling of micro-porous-enhanced surfaces in saturated FC-72 [J].
Chang, JY ;
You, SM .
JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 1996, 118 (04) :937-943
[4]  
Cooper M.G., 1984, Advances in Heat Transfer, V16, P157, DOI DOI 10.1016/S0065-2717(08)70205-3
[5]  
Danilova G.N., 1965, Kholodil'naya Tekhnika, V4, P24
[6]   Nucleate boiling of FC-72 and HFE-7100 on porous graphite at different orientations and liquid subcooling [J].
El-Genk, Mohamed S. ;
Parker, Jack L. .
ENERGY CONVERSION AND MANAGEMENT, 2008, 49 (04) :733-750
[7]   Nucleate Boiling Enhancements on Porous Graphite and Microporous and Macro-Finned Copper Surfaces [J].
El-Genk, Mohamed S. .
HEAT TRANSFER ENGINEERING, 2012, 33 (03) :175-204
[8]   Enhanced nucleate boiling on copper micro-porous surfaces [J].
El-Genk, Mohamed S. ;
Ali, Amir F. .
INTERNATIONAL JOURNAL OF MULTIPHASE FLOW, 2010, 36 (10) :780-792
[9]   Saturation boiling of HFE-7100 from a copper surface, simulating a microelectronic chip [J].
El-Genk, MS ;
Bostanci, H .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2003, 46 (10) :1841-1854
[10]   Influence of thermophysical properties on pool boiling heat transfer of refrigerants [J].
Gorenflo, D ;
Chandra, U ;
Kotthoff, S ;
Luke, A .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2004, 27 (05) :492-502