General Public Exposure by ELF Fields of 150-36/11-kV Substations in Urban Environment

被引:21
作者
Joseph, Wout [1 ]
Verloock, Leen [1 ]
Martens, Luc [1 ]
机构
[1] Univ Ghent, IBBT, Dept Informat Technol, B-9050 Ghent, Belgium
关键词
Electric and magnetic field; electromagnetic (EM) measurement; exposure of general public; extremely low frequency (ELF); safety distance; substation; MAGNETIC-FIELDS;
D O I
10.1109/TPWRD.2008.2002686
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Electromagnetic exposure of the general public due to large substations transforming voltages of 150 and 36 kV to 11 kV is investigated and safety distances for these substations have been determined. In total, 142 field measurements were executed for two substations: 91 measurements of the magnetic field and 51 measurements of the electric field. Measured momentary magnetic-field values are within the range of 0.051 to 13.17 mu T. The levels of the electric field are within the range of 0.095 to 270.0 V/m. The cumulative distribution function of the measured magnetic-field values has been determined, and it is shown that the fields excellently follow a lognormal distribution. The maximal magnetic-and electric-field values for all the investigated substations are below 100 mu T (values over a day and year) and 5 kV/m, respectively. When comparing the average exposure with the value of 0.4 mu T, safety distances of maximally 8.1 m (average day) and 7.1 m (average year) are obtained.
引用
收藏
页码:642 / 649
页数:8
相关论文
共 18 条
[1]  
Ahlbom A, 1998, HEALTH PHYS, V74, P494
[2]   A pooled analysis of magnetic fields and childhood leukaemia [J].
Ahlbom, A ;
Day, N ;
Feychting, M ;
Roman, E ;
Skinner, J ;
Dockerty, J ;
Linet, M ;
McBride, M ;
Michaelis, J ;
Olsen, JH ;
Tynes, T ;
Verkasalo, PK .
BRITISH JOURNAL OF CANCER, 2000, 83 (05) :692-698
[3]  
AHLBOM IC, 2001, ENVIRON HEALTH PER S, V109, P911
[4]  
*ANSI IEEE, 1987, 6441987 ANSIIEEE
[5]  
DAILY WK, 1994, IEEE T POWER DELIVER, V9, P324, DOI 10.1109/61.277703
[6]   MAGNETIC-FIELDS REMOTE FROM SUBSTATIONS [J].
FEERO, WE ;
YONTZ, J ;
DUNLAP, JH .
IEEE TRANSACTIONS ON POWER DELIVERY, 1989, 4 (03) :1862-1868
[7]   ANALYSIS OF 60-HZ MAGNETIC-FIELDS NEAR GROUND-LEVEL IN 187-KV SWITCHYARD OF A 187/66-KV AC SUBSTATION [J].
HAYASHI, N ;
ISAKA, K ;
YOKOI, Y .
IEEE TRANSACTIONS ON POWER DELIVERY, 1992, 7 (01) :237-244
[8]  
ISOKORPI J, 1999, P 11 INT S HIGH VOLT, V2, P107
[9]   Restricting exposure to pulsed and broadband magnetic fields [J].
Jokela, K .
HEALTH PHYSICS, 2000, 79 (04) :373-388
[10]   Measurements of elf electromagnetic exposure of the general public from Belgian power distribution substations [J].
Joseph, Wout ;
Verloock, Leen ;
Martens, Luc .
HEALTH PHYSICS, 2008, 94 (01) :57-66