Comparative study of voltage oriented and frequency coordinated control of grid connected doubly fed induction generator

被引:4
作者
Elhassan, Zakieldeen [1 ]
Yi, Tang [1 ]
Yang, Li [1 ]
机构
[1] Southeast Univ, Sch Elect Engn, Nanjing 210096, Jiangsu, Peoples R China
基金
国家高技术研究发展计划(863计划);
关键词
WIND TURBINES; FIXED-SPEED; SYSTEM; DFIG; MACHINE;
D O I
10.1063/1.4873131
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
In this paper, a comparative study between voltage oriented control (VOC) and frequency coordinated control (FCC) of grid connected doubly fed induction generator (DFIG) is presented. The two method controls are deeply done on DFIG converter sides, grid side converter (GSC), and rotor side converter (RSC). The VOC method permanently maintains the DFIG reactive power to zero values to achieve stable voltage. This control is implemented by regulating the rotor direct axis reference current in RSC using grid reactive power. On the other hand, the FCC has employed the active power obtaining from the system frequency deviation to control the rotor quadrature axis reference current in the RSC. The GSC is the same in two studies, and its applied vector controlled method. The comparison study between the two methods is conducted at a steady and dynamic state under constant and variable wind speeds. The simulation results are carried out by using PSCAD/EMTDC electromagnetic transient program to validate the comparison study between two methods control of DFIG. The outcomes of the simulation show that the VOC is very convenient when the DFIG operated at transient mode and variable wind speeds while the FCC is feasible and effective for steady-state mode applications. Furthermore, the FCC method has an ability to reduce the active and reactive powers ripples as well as decreasing torque harmonics. Both of two methods had fewer transient recovery values of output parameters, which ensure safety dynamic response of DFIG and power system. This study contributes significantly to choose the suitable control of the DFIG converters according to electrical grid operation conditions. In addition, if a joint control has been applied to these two methods, the wind power gained strong and flexible control of the frequency and voltage for different operating conditions. (C) 2014 AIP Publishing LLC.
引用
收藏
页数:17
相关论文
共 34 条
[1]  
Abad G., 2011, DOUBLY FED INDUCTION, V85
[2]   Control of back-to-back PWM converters for DFIG wind turbine systems under unbalanced grid voltage [J].
Abo-Khalil, Ahmed G. ;
Lee, Dong-Choon ;
Jang, Jeong-Ik .
2007 IEEE INTERNATIONAL SYMPOSIUM ON INDUSTRIAL ELECTRONICS, PROCEEDINGS, VOLS 1-8, 2007, :2637-+
[3]   Control of a doubly fed induction wind generator under unbalanced grid voltage conditions [J].
Brekken, Ted K. A. ;
Mohan, Ned .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 2007, 22 (01) :129-135
[4]   Enhancing Frequency Response Control by DFIGs in the High Wind Penetrated Power Systems [J].
Chang-Chien, Lee-Ren ;
Lin, Wei-Ting ;
Yin, Yao-Ching .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2011, 26 (02) :710-718
[5]   Effect of grid voltage and frequency variations on the output of wind generators [J].
Divya, K. C. ;
Rao, P. S. Nagendra .
ELECTRIC POWER COMPONENTS AND SYSTEMS, 2008, 36 (06) :602-614
[6]   Comparison of the response of doubly fed and fixed-speed induction generator wind turbines to changes in network frequency [J].
Ekanayake, J ;
Jenkins, N .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 2004, 19 (04) :800-802
[7]   Comparison of 5th order and 3rd order machine models for doubly fed induction generator (DFIG) wind turbines [J].
Ekanayake, JB ;
Holdsworth, L ;
Jenkins, N .
ELECTRIC POWER SYSTEMS RESEARCH, 2003, 67 (03) :207-215
[8]   Comparative study on the performance of control systems for doubly fed induction generator (DFIG) wind turbines operating with power regulation [J].
Fernandez, L. M. ;
Garcia, C. A. ;
Jurado, F. .
ENERGY, 2008, 33 (09) :1438-1452
[9]   Power system frequency response from fixed speed and doubly fed induction generator based wind turbines [J].
Holdsworth, L ;
Ekanayake, JB ;
Jenkins, N .
WIND ENERGY, 2004, 7 (01) :21-35
[10]   Stator-flux-oriented control of a doubly-fed induction machine with and without position encoder [J].
Hopfensperger, B ;
Atkinson, DJ ;
Lakin, RA .
IEE PROCEEDINGS-ELECTRIC POWER APPLICATIONS, 2000, 147 (04) :241-250