Modeling and Validating the Effective Hydraulic Detention Time for a 10 mgd Ozone Contactor at the Lake Washington Surface Water Treatment Plant, Melbourne, Florida

被引:7
作者
Phares, David E. [2 ]
Rokjer, David M. [1 ]
Crossley, Ian A. [1 ]
Franko, Joseph J. [3 ]
机构
[1] Hazen & Sawyer PC, New York, NY 10018 USA
[2] Water Prod, City Melbourne, Melbourne, FL USA
[3] Hazen & Sawyer PC, Ft Pierce, FL USA
关键词
Ozone; Contactor; Disinfection; CFD; Modeling; CT; Baffling Factor; Melbourne; Cryptosporidium; LT2ESWTR;
D O I
10.1080/01919510902904529
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
Ozonation has been added to the treatment process at the 20 mgd Lake Washington surface Water Treatment Plant (SWTP), Melbourne, Florida to improve finished water quality, control taste and odor, and provide greater than 0.5-log credit for inactivation of Cryptosporidium. The new ozone contactors (2 parallel 10 mgd trains) are located between the existing Actiflo (TM) clarifiers and the filters on a relatively, congested site. Prior to construction, a Computational Fluid Dynamics (CFD) study indicated that the proposed contactor design was not optimized to provide the targeted Cryptosporidium log inactivation. Based on the CFD modeling, the design was modified to reduce the baffle heights (increasing end gaps at turns) and the baffle ends were chamfered to improve flow patterns within the contactor. Internal access platforms were rotated from parallel to the flow (along outside walls) to perpendicular to the flow (along baffle walls). These small design changes increased the modeled effective detention time (t(10)) for disinfection and the corresponding hydraulic efficiency (baffling factor) by 22 %. In addition, the dosing location for the ozone quenching chemical (hydrogen peroxide) was modified to provide extra ozone detention. The ozone contactors were then constructed to incorporate the design changes optimized from the modeling. During the start tip of the ozone system, fluoride tracer tests were completed to validate the effective detention time (and baffling factor) calculated by CFD. Furthermore, a series of modifications are planned for the ozonated water sampling regime to take greater advantage of Ct(10) credits and reduce the required ozone dose, thereby saving energy and operating costs. This paper discusses several calculation methods for Cryptosporidium inactivation Ct(10) reporting in compliance with the Long-Term 2 Enhanced Surface Water Treatment Rule (LT2ESWTR) and the LT2ESWTR Pre- proposal Draft Regulatory Language for Stakeholder Review (USEPA, 2002). The selection of the method will depend upon ease of implementation, modifications required to the ozone-in-water residual sampling system, long-term results of bromate sampling and actual Cryptosporidium bin classification under the LT2ESWTR. The article describes the CFD studies, improvements made to the contactor design, the tracer validation of the design, Ct(10) reporting methods and modifications to the ozone residual sampling system that the City is considering.
引用
收藏
页码:262 / 276
页数:15
相关论文
共 11 条
[1]  
[Anonymous], 2006, FED REGISTER
[2]  
[Anonymous], ADV OZONE OPTIMIZATI
[3]  
[Anonymous], 1991, GUIDANCE MANUAL COMP
[4]  
*AWWA RES FDN, 1999, 90756 AWWA RES FDN
[5]  
COFFEY BM, 2000, 525 AM WAT WORKS ASS
[6]  
COFFEY BM, 1994, ADV APPL OZONE WATER, P125
[7]  
Idelchik I.E., 1996, HDB HYDRAULIC RESIST, VThird
[8]   Cryptosporidium log-inactivation with ozone using effluent CT10, geometric mean CT10, extended integrated CT10 and extended CSTR calculations [J].
Rakness, KL ;
Najm, I ;
Elovitz, M ;
Rexing, D ;
Via, S .
OZONE-SCIENCE & ENGINEERING, 2005, 27 (05) :335-350
[9]  
RAKNESS KL, 1998, OZONE FACILITY OPTIM
[10]  
*US EPA, 2003, 815D03009 US EPA