Axial restraint effects on the fire resistance of composite columns encasing I-section steel

被引:46
作者
Huang, Zhan-Fei [1 ]
Tan, Kang-Hai [1 ]
Phng, Guan-Hwee [1 ]
机构
[1] Nanyang Technol Univ, Sch Civil & Environm Engn, Dept Struct & Mech, Singapore 639798, Singapore
关键词
axial restraint; fire resistance; fire tests; encased I-section steel stanchion;
D O I
10.1016/j.jcsr.2006.07.001
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
This paper presents an experimental study of the axial restraint effect on fire resistance of four unprotected encased I-section composite columns. Axial restraints were applied to simulate thermal restraints from adjoining cool structures onto a heated composite column in a compartment. These real-sized 3.54 m long columns were subjected to concentric axial force at a load ratio of 0.7 at normal ambient temperature. Different degrees of axial restraint are investigated. An electric furnace was used to apply four-face heating condition on the columns for approximating a realistic fire scenario. All columns failed in flexural buckling mode. In the later part of the paper, finite element simulations were conducted to compare with test results. Numerical predictions of both temperature distribution and structural response during heating agree reasonably well with experimental data. Both test results and numerical analyses show that axial restraint significantly reduces the column fire resistance. Moreover, it was also observed that during heating all specimens underwent concrete spalling at mid-height, which noticeably decreased the fire resistance. Column critical times are also predicted according to Eurocode 4 Part 1.2, which are consistently shorter than the numerical predictions. (c) 2006 Elsevier Ltd. All rights reserved.
引用
收藏
页码:437 / 447
页数:11
相关论文
共 27 条
[1]   Structural performance of rotationally restrained steel columns in fire [J].
Ali, F ;
O'Connor, D .
FIRE SAFETY JOURNAL, 2001, 36 (07) :679-691
[2]  
ANDERBERG Y, 1976, FIRE EXPOSED HPERSTA
[3]   The influence of the thermal expansion of beams on the structural behaviour of columns in steel-framed structures during a fire [J].
Bailey, CG .
ENGINEERING STRUCTURES, 2000, 22 (07) :755-768
[4]  
BAZANT ZP, 1979, MAG CONCRETE RES, V31, P67
[5]  
Faris AA, 1998, J CONST STEEL RES, V46, P1, DOI [10.1016/S0143-974X(98)80036, DOI 10.1016/S0143-974X(98)80036-9]
[6]  
FRANSSEN JM, 2000, USERS MANUAL SAFIR20
[7]   Compressive and flexural behaviour of concrete filled steel tubes after exposure to standard fire [J].
Han, LH ;
Huo, JS ;
Wang, YC .
JOURNAL OF CONSTRUCTIONAL STEEL RESEARCH, 2005, 61 (07) :882-901
[8]   Tests on cyclic behavior of concrete-filled hollow structural steel columns after exposure to the ISO-834 standard fire [J].
Han, LH ;
Lin, XK .
JOURNAL OF STRUCTURAL ENGINEERING-ASCE, 2004, 130 (11) :1807-1819
[9]   Experimental study and calculation of fire resistance of concrete-filled hollow steel columns [J].
Han, LH ;
Zhao, XL ;
Yang, YF ;
Feng, JB .
JOURNAL OF STRUCTURAL ENGINEERING, 2003, 129 (03) :346-356
[10]  
HAN LH, 2001, J CONSTR STEEL RES, V0057